Omega Vehicle Security LV-510 User Manual

Page 3

Advertising
background image

 

 

ELECTRICAL  

Step Two 

Signal Outputs (Normally Open vs. Normally Closed):  The LV‐510 series float switch ships from the factory in 
the  Normally  Open  (NO)  configuration.    The  normal  state  is  when  the  float  is  resting  on  the  bottom  of  the 
stem.  An orientation mark will appear on the top of the float when it is in the NO configuration.  To switch the 
LV‐510 series from NO to NC configuration, flow the steps below. 

1. Remove the C‐clip from the stem. 
2. Remove the float and rotate it 180°. 
3. Return the float to the stem with orientation mark now on the bottom. 
4. Replace the C‐clip. 

Normally Open Operation

Normally Closed Operation

Orientation  mark  on  the  top  of  the  float.    In  the  dry 
state,  the  float  rests  on  the  bottom  of  the  stem  and 
the circuit is open. 

 

Orientation  mark  on  the  bottom  of  the  float.    In  the 
dry  state,  the  float  rests  on  the  bottom  of  the  stem 
and the circuit is closed. 

As  the  switch  becomes  wet,  the  float  becomes 
buoyant and circuit closes. 

 

As  the  switch  becomes  wet,  the  float  becomes 
buoyant and circuit opens. 

Contact Protection (Reed Switch):  When current is interrupted, the inductance of the load generates a high 
frequency  voltage,  which  appears  across  the  switch  contacts.    If  the  voltage  is  large  enough,  it  can  cause 
arcing.  Arcing can cause the contacts to weld to each other resulting in unreliable switching performance.  It is 
essential  to  protect  the  circuit,  by  suppressing  the  voltage  to  prevent  arcing.    This  can  be  accomplished 
through the use of a diode for DC circuits and a resistor‐capacitor network for AC circuits. 

DC Contact Protection: 

 

AC Contact Protection: 

 
 
 