Readjusting input / output, Signal output jumpers – Omega Vehicle Security DRF-RES Series User Manual

Page 8

Advertising
background image

Page 8

User’s Manual Series DRF

6-READJUSTING INPUT / OUTPUT

To change the input/output relation of the
instrument, proceed as indicated below :

(Following values in brackets are examples for
readjusting the input/output relation of the instrument
to 0/100% = 0/10 Vdc and input type potentiometer)

1.- Open the front cover

2.- Select the required input jumpers

(Section

4, page 6)

3.- Select the required output jumpers

(Section

5, page 7)

4.- Connect a potentiometer to the input
terminals

(Section 3, page 5)

5.- Connect a multimeter to the output terminals

(4 and 5 for mA or 4 and 6 for Vdc)

6.- Generate the low input signal

(0%)

Operate the OFFSET potentiometer, until
the low output value is reached

(0Vdc)

7.-

Generate the high input signal

(100%)

Operate the SPAN potentiometer, until the
high output value is reached

(10Vdc)

8.- Repeat 6 and 7 to improve the accuracy
until it reaches its specified value

9.- Close the front cover

IMPORTANT - Opening the
front cover may grant access
to areas with dangerous

voltages. Operations must be
performed by qualified
technical staff.

5-SIGNAL OUTPUT JUMPERS___

The position of the output jumpers selects
the range for the output signal as indicated
below.

0/1 V

DC

0/10 V

DC

4/20 mA
0/20 mA

J1

J2

J3

J4

J5

J6

Advertising