Output wiring, Mov recommended solenoid – Omega DPF76 User Manual

Page 20

Advertising
background image

15

OUTPUT WIRING

The following diagrams detail the connection of the relay and analog output options. Each relay consist of a form A contact
(Normally Open). NPN transistor or Normally Closed contacts are available with solder jumpers (see Jumper Options).

SOLENOID (Single Stage)

Use Relay A (pins 1 & 2) for single stage preset. When the count or rate (selectable) reaches Preset A, Relay A will
energize. When Relay A closes, current passes through the solenoid for activation. When operating AC solenoids,
we recommend the use of an MOV to reduce inductive kickback (use a diode for DC solenoids).

ANALOG OUTPUT

The analog output can be selected to output 4-20 mA or 0-20 mA and can be selected to track the rate or count.
Pin 13 supplies 12 to 18V to power the current loop. Pin 14 supplies the current sinking driver. When connecting
a strip chart recorder, make connections as follows:

ALARMS

The relays can be used to trigger alarms which warn the operator that a batch is complete or the rate has
exceeded a set speed. The outputs are programmable to be assigned for rate or count. When assigned to the
count, the relays can have a user selectable on time (duration) or can be latched until reset.

MOV
recommended

SOLENOID

PNP

Prox Sensor

BLK

BRN
BLU

1 COMMON

2 N.O.(N.C./NPN)

3 COMMON

4 N.O.(N.C./NPN)

5 INPUT A

6 INPUT B

7 11 - 19 V @ 50mA OUT/+DC IN

8 -DC (GROUND)

9 RESET INPUT

10 6 - 14 V @ 50mA

11 A.C. INPUT

12 A.C. INPUT

RELA

YS

A

B

13 V+

14 I SINK

ANALOG

OUTPUT

ON

CAL.

0-20mA

COUNT

SET

OFF

RUN

4-20mA

RATE

RUN

1 2 3 4

ON

SWITCH

GND

+12V

STRIP CHART

RECORDER

TURBINE FLOWMETER

PULSE OUTPUT

-

+

1 COMMON

2 N.O.(N.C./NPN)

3 COMMON

4 N.O.(N.C./NPN)

5 INPUT A

6 INPUT B

7 11 - 19 V @ 50mA OUT/+DC IN

8 -DC (GROUND)

9 RESET INPUT

10 6 - 14 V @ 50mA

11 A.C. INPUT

12 A.C. INPUT

RELA

YS

A

B

13 V+

14 I SINK

ANALOG

OUTPUT

ON

CAL.

0-20mA

COUNT

SET

OFF

RUN

4-20mA

RATE

RUN

1 2 3 4

ON

SWITCH

LIGHT

BELL

1 COMMON

2 N.O.(N.C./NPN)

3 COMMON

4 N.O.(N.C./NPN)

5 INPUT A

6 INPUT B

7 11 - 19 V @ 50mA OUT/+DC IN

8 -DC (GROUND)

9 RESET INPUT

10 6 - 14 V @ 50mA

11 A.C. INPUT

12 A.C. INPUT

RELA

YS

A

B

13 V+

14 I SINK

ANALOG

OUTPUT

ON

CAL.

0-20mA

COUNT

SET

OFF

RUN

4-20mA

RATE

RUN

1 2 3 4

ON

SWITCH

Advertising