Omega FMA 4000 User Manual

Page 32

Advertising
background image

28

8.3

ASCII Commands Set

OMEGA FMA 4000 SOFTW

ARE INTERF

ACE COMMANDS

COMMAND

NAME

DESCRIPTION

No.

COMMAND SYNT

A

X

Command

Argument 1

Argument 2

Argument 3

Argument 4

Response

Flow

Requests the current flow

sensor reading in current EU

1

F

<V

alue> (Actual flow in

current engineering units)

Diagnostic

Enable / Disable LCD

Diagnostic messages (only

for LCD option).

Request current status of

the Diagnostic events, LED

status and LCD diagnostic

mode (enabled/disabled).

2

D

E

(enable LCD

** Diagnostic Messages)

D:E

D

(disable LCD

** Diagnostic Messages)

D:D

NO ARGUMENT

(read current status of

the diagnostic word)

D:0x0,L:9,E

0x0 – diagnostic word

9 - current LED status

E - LCD mode (enabled)

Roll back to

N

2

feature.

Enable / Disable Roll back

to N

2

feature.

3

N

E

(enable Roll back to N

2

)

N:E

D

(enable Roll back to N

2

)*

N:D

NO ARGUMENT

(read current mode of

the N2 Roll back )

N:D

Or

N:E

Gas Select

Selects one of the ten

primar

y gas calibration

tables to use. T

ables are

entered via the MEM

commands at time of

calibration.

4

G

0 (gas 0)*

to

9 (gas 9)

G0 through G9,

<Gas Name>

NO ARGUMENT

(read status)

G0 through G9,

<Gas Name>

Note: An “*” indicates power up default settings. An “**” indicates optional feature not available on all models.