P2 p1, Burner pressure c.h. and d.h.w, Fig. 22 – Optima Company 1001 User Manual

Page 21: Fig. 23

Advertising
background image

1001

21

Burner Pressure C.H. and D.H.W.

8.6

To Range Rate the Boiler C.H. (not required for standard installations).
The boiler can be range rated for an output from 11.8 kW up to 27.9 kW. When the boiler is supplied
it is factory set at the maximum output 27.9 kW.
Procedure
a. Release the control panel fixing screws (fig. 30) and lower panel.
b. Loosen the screw in the burner pressure test point (fig. 22) and attach a gauge.
c. Switch on the electricity supply to relight the main burner.

Fig. 22

Balance tube

Modureg

Gas valve

Test point burner pressure

Gas inlet pressure test point

Fig. 23

Note 1 - Modulation is available on central heating, so
the procedures must be carried out while the system
is relatively cold. Recheck boiler thermostat is set to
maximum.

d. Adjust the potentiometer P1 on the PCB (fig. 24) in
the control panel until the required burner pressure is
obtained (Anticlockwise to reduce the pressure).

Note 2 - The range of inputs with corresponding
burner pressure is given on the Data badge which is
situated behind the top front panel. Further informations
is on (fig. 23).

e. With the pressure set, turn off the electrical supply
and mark the set input on the Data badge (with sticker
supplied).

Burner Pressure C.H. and D.H.W.
P1 =
C.H. range rating to be set on site
P2 =D.H.W. temperature (factory set, not to be
adjusted)
P1 Adjust with screwdriver!

12

1

TR1

X4

X6

2

3

4

X2

RY1

X1

2AT

230V
50Hz

1

11 10

7

2

6

3

5

12

9

10

1

2

P1

X3

6

5

3

4

1

F1

9 8 7 6 5 4 3 2 1

X8

1

2

3

4

5

6

7

8

9

X5

1

2

X7

JP4

13

L7

RY2

RY4

JP1

P2

P2

P1

MIN

MAX

MIN

MAX

Pressure

Minimum

Maximum

settings

mbar

mbar

Natural Gas

3.0

15.0

L.P.G.

6.9

34.5