Normal operating codes, Fault codes/ troubleshooting – True Manufacturing Company Swing Glass Door Merchandiser Refrigerator GDM-26 User Manual

Page 8

Advertising
background image

2001 East Terra Lane • O'Fallon, MO. 63366 • ph. 636.240.2400 • toll free 800. 325.6152 • [email protected]

GDM SERIES COOLER EQUIPPED WITH EMS (ELSTAT) CONTROL

NORMAL OPERATING CODES

Normal operating mode. Cabinet

should be holding proper product

temperature.

Units is in Standby mode. Control

will cycle the unit at a warmer

temperature. Lights will be off.

Units is in defrost . Compressor has

been shut off and evaporator fan

motor is running to clear any ice

that may have accumulated. This is a

predetermined program function.

Freeze up protection. This unit has

gone down below the minimum

temperature Set Point.

Possible Problems

Action to take

Compressor not shutting off

Check compressor. Relay at

controller

Faulty Probe

Ohm out evaporator probe

Parameters have been

changed

Check parameter list

Refrigeration System Failure. The unit

has not satisfied the set point in the

amount of time allowed.

Possible Problems

Action to take

Unit is not cooling

Check the Refrigeration System

Faulty Probe

Ohm out evaporator probe

Faulty Controller

Bypass control to see if system will

run

Parameters have been

changed

Check the parameter list

Power supply voltage is low.

Possible Problems

Action to take

Poor voltage at outlet

Verify proper voltage to cabinet

Faulty Transformer

Verify 120V to transformer. Check for

12V on secondary. Connector 7
(see page 2)

Faulty Controller

Bypass control to see if system will run

Faulty Elstat

If 12V is present at connector 7, replace

Elstat

Power supply voltage is too high.

Possible Problems

Action to take

High voltage at outlet

Verify proper voltage to cabinet

Faulty Transformer

Verify 120V to transformer. Check for

12V on secondary. Connector 7
(see page 2)

Faulty Elstat

If 12V is present at connector 7, replace

Elstat.

Probe failure

Possible Problems

Action to take

Connector off at controller Verify that connector 4 is in place

(see page 2)

Probe is open

Ohm out probe

Probe is shorted

Ohm out probe

Probe wire is open

Ohm out probe wire

Elstat Probes by the evaporator motor GDM-10 to 33 probes in air

stream GDM-35 to 72

Value

Ohms

32°

32,000 Ohms

70°

12,000 Ohms

80°

9,300 Ohms

85°

8,500 Ohms

90°

7,000 Ohms

FAULT CODES/ TROUBLESHOOTING

8