Toshiba PROFIBUS-DP PBDP-110 User Manual

Page 10

Advertising
background image

9

Global Control Functions

Freeze mode: Input (monitor) data values are held constant within the PBDP-110

until the next “freeze” command or an “unfreeze” command is
received. Used primarily for synchronized monitoring of multiple
Profibus nodes.

Sync mode:

Output (control) data values are held constant within the PBDP-
110 until the next “sync” command or an “unsync” command is
received. Used primarily for synchronized control of multiple
Profibus nodes.

Clear_Data:

All output (control) data values are cleared to “0”.



Network Watchdog

A network watchdog function is always operating within the PBDP-110. In the event
of a disconnection from the Profibus network or loss of the network master, the
PBDP-110 can automatically switch any attached drives over to local control (if
selected at time of unit commissioning).


Indicators

1 green LED is provided to indicate when the PBDP-110 has achieved the
DATA_EXCHANGE state with the Profibus network master. This serves as a
convenient indicator that the Profibus master and PBDP-110 are configured
properly and are exchanging data.

1 green LED on the MMI interface port. The context is application-specific,
but under normal operation blinks at a 0.5Hz rate as a “heartbeat” indicator.
Also indicates data transfer when used with the Flashloader programming
utility.

1 green LED on each of the Channel A and Channel B drive connectors,
which indicate that the port is receiving power from the corresponding drive.



Profibus Network Connector

The network interface is a standard DB9 female connector with the following signals
provided:

Pin

Number Function In/Out

3

Profibus network “B” (positive) data line

In/out

4

RTS signal – direction control for fiber optic network
interface

Out

5

DGND – power supply ground internally connected to the
interface board’s isolated ground

-

6

VP – power supply +5v internally connected to the
interface board’s isolated P5.

-

8

Profibus network “A” (negative) data line

In/out

9

RTS signal ground reference – internally connected to the
interface board’s isolated ground

-

1, 2, 7

No connection

-