Output Frequency

Drive parameter number FD00. Continuously reports the drive’s operating frequency.
In order to determine the drive’s actual output frequency, the data contained in the
output frequency word offsets must first be converted from hexadecimal to decimal,
and then divided by 100. For example, if the output frequency high byte is 0x12 and
the output frequency low byte is 0x34, then 0x1234 converted to decimal is 4660.
Dividing this number by 100, the actual operating frequency of 46.60Hz is obtained.


Output Current

Drive parameter number FE03. Continuously reports the drive’s output current in %.
In order to determine the drive’s actual output current, the data contained in the
output current word offsets must first be converted from hexadecimal to decimal, and
then divided by 100. For example, if the output current high byte is 0x23 and the
output current low byte is 0x15, then 0x2315 converted to decimal is 8981. Dividing
this number by 100, the actual output current of 89.91% rated drive current is
obtained.


Output Voltage

Drive parameter number FE05. Continuously reports the drive’s output voltage in %.
The actual output voltage calculation method is identical to that for output current
given above.


Action Bits / Parameter Number

Parameter action bits and 16-bit parameter register number. Refer to section 10 for
a detailed explanation of these items.


Parameter Data

During parameter register reads, this word contains the requested data response.
Refer to section 10 for a detailed explanation of this data word


Again, in case of any discrepancies, documentation provided by the drive
manufacturer supercedes the examples given here.