TIC-LF494B

4

• Digital output: OFF
• LCD display: No display
• PROFIBUS: No communication

Power supply:

One of the following can be selected:

• 100 to 240Vac, 50/60Hz (std.)

(allowable voltage 80 to 264Vac)

• 24Vdc (allowable voltage 18 to 36Vdc)

• 110Vdc (allowable voltage 90 to 130Vdc)

Surge protection:

Arresters are installed in the power supply, and a
current signal output circuit to help protect the
meter from lightning and improve personnel
safety.

Case: Aluminum alloy (equal to IP 67)
Coating: Acrylic resin-baked coating, pearl-gray

colored

Cable connection ports:

Cable glands

LF610 and LF612 without cFMus Approval:

Provided as standard, OD of cable
11~13mm
Material Nylon 66
G (PF) 1/2 male screws.

LF610F and LF612F with cFMus Approval:

Not provided, 1/2–14NPT male screws are
required.

Applicable diameter

0.433 to 0.512 inch (11 to 13mm)

Note: When PROFIBUS option is specified, cable gland size

is φ6~8mm for signal cable, φ11~13mm for power
cable

Vibration resistance:

No resonance to the following levels of

vibration:

• 10 to 150Hz with acceleration of 9.8m/s

2

• Vibration of 30Hz with 29.4 m/s

2

in 4h in each

direction will not cause any defect to unit.

Note: Avoid using the flowmeter in an environment with

constant vibration.

Dimensions and Weights:

See Figure 8 (for Separate type)

MTBF:

Converter: 220,000 hours (25 years) at 77 °F

(25 °C) based on strict military
specification MIL-HDBK-217F

Detector: 350,000 hours (40 years) at 77 °F

(25 °C) based on strict military
specification MIL-HDBK-217F