119076.02 TELEPRESENCE T3 ROOM REQUIREMENTS 12.08

TANDBERG

Telepresence T3

POWER OUTlET fUSE

REQUIREMENTS

The following minimum power outlet fuse requirements apply to the TANDBERG
Telepresence T3:

ITEM

WATT

PlACEMENT

fUSE

ON/Off SWITCH

T1 Module × 3

2400

Back wall

A

1

Presentation

splitter × 2

60

Back wall

A

1

Table power outlet × 6

2400

Back wall

B

2

TCU

400

Back wall

C

2

Table quick buttons

50

Back wall

C

2

Presentation input

switch

5

Back wall

C

2

Touch collaboration

display splitter

20

Back wall

C

2

Touch collaboration

display

750

Back wall

C

2

Document camera

300

Ceiling

D

2

T3 Ceiling mounted

lights

750

Ceiling

D

3

T3 LED Module

1000

Back- / Front wall

D

4

Total power

9335

Note!

The table lists minimum fuse

requirements. All electrical work must
be done by electricians with local
knowledge.

Note!

Outside the room—adjacent to the

entrance—there shall be an emergency
power switch to switch off the power to
the entire system and the room.

On the inside adjacent to the exit there
shall be a sign with the following text:

fire emergency switch is

located on the outside of

this room.