G8000 Series Installation and operation Manual

FIGURE 11.10 - EARTH GROUND WIRE

G8000 - 100 kVA

12 mm or 1/2 in.

Terminal

10 mm or

7/16 in. bolt

Feed-through opening

AwG 2 (38 mm)

ground wire

To facility

earth ground

Ground bus

G8000 - 300 kVA

Through knockout plate

on top (recommended)

Alternate ground

wire location

note: Use either the top or the

bottom grounding point, but not

both. Doing so may degrade the

performance of the unit.

10 mm or

7/16 in. bolt

Facility earth ground.

Ground wire routing through

top knockout plate.

Ground bus

G8000 - 150/225 kVA

Ground bus

12 mm or 1/2 in.

Terminal

10 mm or

7/16 in. bolt

Feed-through opening

AwG 2 (38 mm)

ground wire

To facility

earth ground

Facility earth ground.

Alternate ground wire routing

through top knockout plate.

note: Use either the top or the

bottom access for the ground

wire to connect to the ground

buss, but use only one ground

wire..