41

G8000 Series Installation and operation Manual

11.7.2 Grounding Configuration (without input neutral)

when the input source is wye-connected, the neutral line out to the bypass input should be left open. The

UpS is grounded by connecting the neutral terminal to the ground bus with the internal jumper cable. See

Figure 11.14.
The jumper cable should stay in place. See Figure 11.13 for the jumper cable location.
If a ground fault interrupter is installed, the UpS is likely to trip the interrupter during transferring to/from

the bypass circuit. It is recommended that the ground fault interrupter be set to a minimum delay of 0.5

seconds.

FIGURE 11.14 - GROUNDING CONFIGURATION WITHOUT INPUT NEUTRAL

11.7.3 Recommended Configuration (for delta-input)

If the input source is a delta-connection (3-phase 3-wire) without ground, the neutral terminal in the UpS

cabinet must be connected to the ground bus with the internal jumper cable as shown in Figure 11.15.
The jumper cable should stay in place. See Figure 11.13 for the jumper cable location.

FIGURE 11.15 - GROUNDING CONFIGURATION FOR NON-GROUNDED DELTA-INPUT

n

G

3

Ǿ

3

Ǿ

3

Ǿ

n

G

< UpS Cabinet >

n

3

Ǿ

3

Ǿ

G

Input Source

remove

Jumper Cable

G

n

3

Ǿ

To the

load

n

G

3

Ǿ

3

Ǿ

3

Ǿ

n

G

< UpS Cabinet >

n

3

Ǿ

3

Ǿ

G

Input Source

Jumper Cable

remains in place

G

n

3

Ǿ

To the

load

n

G

3

Ǿ

3

Ǿ

3

Ǿ

n

G

< UpS Cabinet >

3

Ǿ

3

Ǿ

G

Input Source

Jumper Cable

remains in place

G

n

3

Ǿ

To the

load

n

G

3

Ǿ

3

Ǿ

3

Ǿ

n

G

< UpS Cabinet >

G

n

3

Ǿ

3

Ǿ

To the

load

output Distribution

3

Ǿ

3

Ǿ

G

Input Source

b

Ǿ

remove

Jumper Cable

n

G

3

Ǿ

3

Ǿ

3

Ǿ

n

G

< UpS Cabinet >

n

3

Ǿ

3

Ǿ

G

Input Source

remove

Jumper Cable

G

n

3

Ǿ

To the

load

n

G

3

Ǿ

3

Ǿ

3

Ǿ

n

G

< UpS Cabinet >

n

3

Ǿ

3

Ǿ

G

Input Source

Jumper Cable

remains in place

G

n

3

Ǿ

To the

load

n

G

3

Ǿ

3

Ǿ

3

Ǿ

n

G

< UpS Cabinet >

3

Ǿ

3

Ǿ

G

Input Source

Jumper Cable

remains in place

G

n

3

Ǿ

To the

load

n

G

3

Ǿ

3

Ǿ

3

Ǿ

n

G

< UpS Cabinet >

G

n

3

Ǿ

3

Ǿ

To the

load

output Distribution

3

Ǿ

3

Ǿ

G

Input Source

b

Ǿ

remove

Jumper Cable

Advertising