rost and overheating protections - Pump operation can be manipulated by the user in
both collector stagnation and frost conditions. This set-up is possible in System Guard,
SGUARD, Men domain.

Overheating protection (CET) – The Circulation pump may not be powerful enough to circulate
the heat transfer fluid in the solar loop with air pockets. User can program the pump to stop at a
desired maximum collector temperature, shown by

? symbol, to protect the pump. USDT 2004

will take over the normal operation after the temperature decreases to an acceptable working
temperature, shown as

=. This feature (ON) can be disabled by user to (OFF). Factory setting

is 260

o

F to stop the pump. The pump starts again at 230

o

F. Customer in field can change these

settings.

Frost Protection – Frost protection in the sun-belt region is provided by circulating water in the
solar loop when freezing conditions exist. Regardless of the temperature difference ? T, the
circulation pump runs when the collector temperature is below a programmable minimum
temperature, shown by

= symbol. The pump stops as soon as the temperature in the solar loop

reaches a safe region programmed by the

? symbol. This feature is disabled at the factory and

displayed as (OFF).

min

= Pump runs below this temperature (factory setting 35 F)

min

? Pump stops above this temperature (factory setting 39 F)


tart functions - The Circulation pump can be programmed to start on a low insolation
level. The Start function feature is useful when heat transferred to the collector sensor is

not fast enough for an early start; especially when the collectors are flat mounted.

The enabled start function runs the pump at a given solar radiation or programmed temperature
difference. The feature is disabled at the factory.

START

Start function screen

ON

Enable start function

OFF

Disable start function


If this feature is selected, following parameters must be adjusted for proper operation:

GBS

Pyranometer port designation (radiation monitoring sensor port)

1

Sensor 1

2

Sensor 2

3

Sensor 3

--

Manual input in next step

INS

Radiation threshold in W/m

2

CIRC

Pump runtime in seconds

INT

Maximum interval time in second

FLU

Number of flushes


The following example activates the circulation pump at 200 W/m

2

and runs it for 15 seconds. If

rT condition is met within the time period, the pump stays on.

INS

20

CIRC 15

F

S