CHANGING FACTORY SETTINGS:

Temperature differentials and manual operation of pump




Par Mode is USDT 2004's basic program; it uses two sensors to control a simple solar
water heating system. The unit is already factory set with ON/OFF pump temperatures.
However, these temperatures may be altered if required
:

Par

Using the navigation key

^_ allows you to select the desired parameter while you are in

the program mode. Press the selection key

ò once to select the parameter in the window.

Selected parameter blinks allowing you to modify it. You can modify the selected parameter while
the middle window blinks by pressing the

ï or ð key. The unit accepts the new value by pressing

the

ñ key once. Please make sure that you are in Par mode.

RUV 3.5 – Displays the software revision number corresponding to this manual.
PR O – Inapplicable


PROGRAMMING THE TEMPERATURE RANGE

USDT 2004 is factory set at approx T2 > 161

o

F PUMP OFF, T2 < 150

o

F PUMP ON. Once Par

mode has been accessed, using Code 32 as illustrated above, the user may program a different
temperature range. There are two temperatures that should be entered: