Figure 5 m-2001 and m-2299 typical connections – Toshiba M-2001 Series User Manual

Page 14

Advertising
background image

–7–

M-2299 Application Guide

M-2299

ADAPTER PANEL

FUNCTIONS

TB1

VOLTAGE REDUCTION STEP #2 CONTACT

VOLTAGE REDUCTION
STEP #1 CONTACT

NEUTRAL LIGHT SWITCH

OPERATIONS COUNTER

SWITCH

LINE
CURRENT

CT

CT

SHORTING SWITCH

NEUTRAL
LIGHT

+12 V dc WETTING SUPPLY

AUTO DISABLE

MANUAL RAISE

MANUAL LOWER

SELF-TEST ALARM (RETURN)

USER-PROGRAMMABLE ALARM (RETURN)

VOLTAGE IN
FUSE (1/4 A)

AUTO

INT

EXT

TO

CONTROL

INT

EXT

MANUAL

MANUAL LOWER

MANUAL RAISE

NO

NC

M-2001

TAPCHANGER

CONTROL

FUNCTIONS

VOLTAGE IN
(REGULATED
120 V)

NEUTRAL

MOTOR

OP

COUNTER

VOLTAGE IN

TEST
TERMINAL
FUSE 3A

FRONT PANEL INPUTS

NEUTRAL

+12 V dc

16

17

18

19

20

21

22

23

24

25

26

27

1

2

7

8

10

12

14

15

3

4

5

9

11

13

6

L

R

Toshiba Terminals

M-2299 Terminals

TB1

TB2

LOCAL/REMOTE

SELF-TEST ALARM (POLARITY)

USER-PROGRAMMABLE ALARM (POLARITY)

METER OUT

POLARITY CONTACT

MOTOR POWER
FUSE (6 A)

2

3

1

10

5

4

12

1

OFF (MOM)

OFF

OFF

OFF

20, 21 or 22

on T.C.

See Note

11

N/U

N/U

MOTOR POWER

6

8

7

RESISTOR NETWORK WIPER

POSITION RESISTOR

9

NOTE: The self-test alarm and user-programmable alarm contacts are shown in the de-energized state (no

voltage applied). The self-test alarm contacts open after the M-2001 passes the self-test; the
user-programmable alarm contacts close when an alarm is recognized.

8 WARNING: In no case should the line current circuit be interrupted with the regulator or transformer
energized.

Do not remove auxiliary current transformers without shorting the current inputs. Death or severe
electrical shock can occur.

Figure 5

M-2001 and M-2299 Typical Connections