2 m-2001 checkout procedure, Basic operational test, 3 in-service test – Toshiba M-2001 Series User Manual

Page 20: 0 checkout procedure, 1 power

Advertising
background image

–13–

M-2299 Application Guide

5.2

M-2001 Checkout Procedure

NOTE: This test of the M-2001 assumes that the

unit remains connected to the adapter panel.

Basic Operational Test

1.

Apply 120.0 V ac to TB1-9 (motor power)
and TB1-10 regulated voltage) of adapter
panel.

2.

Connect neutral to TB1-8 (neutral).

3.

Verify local voltage equals input voltage
±0.3 V.

4.

Apply 100.0 mA in-phase current to
TB1-14 (load current-polarity) and
TB1-15 (load current-return) of the
adapter panel. Verify Control Load

IIIII

equals 100 mA and Power Factor equals
1.0 ±0.02.

5.

Verify UP, DOWN and ENTER buttons
work.

—Checkout Procedure Complete—

5.3

In-Service Test

1.

Set the M-2001 Tapchanger Control to
display Bias Voltage screen.

2.

Press ENTER.

3.

Use UP and DOWN buttons to cause
RAISE and LOWER outputs.

—In-Service Test Complete—

Return unit to desired settings

6.0

Checkout Procedure

NOTE: All Beckwith Electric units are fully

calibrated at the factory. There is no need to
recalibrate the units before initial installation.

Set the AUTO/OFF/MANUAL switch to OFF.
Inspect the MOTOR POWER and VOLTAGE fuses
to ensure they are correctly sized and have not
blown.

6.1

Power

1.

Remove any external connection
between TB1-9 and TB1-10 which are
located on the adapter panel printed
circuit board. Also remove any voltage
applied to TB1-9 externally. Using a
voltmeter, make sure that the voltage
applied to TB1-10 is nominal 120 V ac
with respect to TB1-8 (neutral). Apply
power to TB1-10 (hot) and TB1-8
(neutral).

8 WARNING: Voltage applied at the METER OUT
test terminal may energize the regulator or
transformer to a high voltage through the
voltage transformer.

Death or severe electrical shock can occur.

Do not connect any voltage source at the METER
OUT test terminal.

2.

Connect a voltmeter to the METER OUT
test terminal on the front of the adapter
panel. 120 V ac should be indicated.

CAUTION: Do not reverse the ground and hot
wires when connecting an external source. A 3 AG
fuse (F2) is installed to protect the relay from
damage if these connections are accidentally
reversed. Spare fuses are supplied inside the fuse
holders. Units returned with only a blown fuse are
not covered by warranty, and a nominal repair charge
will be made for replacement of the fuse. Please
check the fuse before returning the unit for repair, in
order to avoid unnecessary repair charges.

Advertising
This manual is related to the following products: