7


UDP Receive:

RECV instruction is used,

[ A RECV B ]

A

: H3100 (fixed)

B

: Result status

A+1

: UDP receive command (H0033)

B+1

: Error code

A+2

: Socket number (1 to 12)

A+3

: Sender IP address (note 1)

A+4

: Ditto

A+5

: Sender Port number

A+6

: Receive data word size (1 to 1000)

A+7

: Destination data table register type (note 2)

A+8

: Destination data table register starting address

A+9

: Timeout setting (0.1s units, see note 3)

Note 1: If sender IP address is 192.0.0.5 (HC0.0.0.5), set as follows.

A+3 = H0005
A+4 = HC000

For broadcast receiving, set 0.0.0.0.
Note 2:

RW register = 3
D register = 4

Note 3: If A+9 = 0, there is no timeout.

Sample program














12544 = H3100
51 = H0033
Socket number = 2
Sender IP address = 192.0.0.5 (-16384 = HC000)
Sender Port number = 5000
Receive word size = 100
Destination data table is D2000 and after, no timeout setting