Specifications, Order numbers – Toshiba Eagle T1 Series PLCs User Manual

Page 2

Advertising
background image

SPECIFICATIONS


ANALOG INPUTS

ITEM

SPECIFICATION

Part Number:

See Order Numbers Below

I/O Registers Assigned:

None (Uses Data Registers, 1 Register per Channel Designated by Sfwr)

Input Range: Thermocouple

Resolution

J, K, R, S, T, E, N, & B . 0-100 mV, Cold Junction Compensation Error
1

°

maximum, 0.5

°

C typical.

Input Range: RTD

Resolution

PT100 (0.00395 and 0.00385), 3 Wire Compensation, Current Sense
0.5ma. Range: -200

°

to 800

°

C

Input Range: Voltage

Current

Resolution

0-100 mV, 0-10 V (via PLC scaling/external shunt resistor)
0-20 mA
12 bit


ANALOG OUTPUTS

ITEM

SPECIFICATION

Part Number:

See Order Numbers Below

I/O Registers Assigned:

None (Uses Data Registers, 1 Register per Channel Designated by Sfwr)

Output Range: Voltage

Current

0-10 V, Minimum Load = 400

4-20 mA Maximum Load = 500


GENERAL

ITEM

SPECIFICATION

Communication Ports: PLC

IBM

Connects to T1 Programming Port
Connects to Computer for Setup Connects to OIS for PLC Access

Temperature:

Operating: 0

°

to 50

°

C Storage: -25

°

to 80

°

C

Humidity:

10% to 90% Non condensing

Immunity to ESD:

Level 3 per IEC 61000-4-2

Immunity to Transients:

Level 3 per IEC 61000-4-4

Radiated Susceptibility:

Level 3 per IEC 61000-4-3

Emissions:

EN55011 CISPR A

Certifications:

CE, CSA

Isolation:

Analog isolated from Digital, no isolation between channels.

Size

Eagle 0800 & 0404 155mm x 102mm x 48mm
Eagle 0201 94mm x 42mm x 47 mm

Mounting:

DIN rail or through hole

Weight

Eagle 0800 & 0404: 0.5 kg Eagle 020:1 02 kg


ORDER NUMBERS

ITEM

DESCRIPTION

Eagle0201U

2 Universal Analog Inputs, 1 Analog Output.

Eagle0404U

4 Universal Analog Inputs, 4 Analog Outputs.

Eagle-0800U

8 Universal Analog Inputs.

TKEAGLE05T1

Cable, 50 cm, Connects T1 to Eagle Exp.Unit

TKEAGLE20T1

Cable, 2 m, Connects T1 to Eagle Exp.Unit1

TKEAGLE20T2

Cable, 2 m, Connects T2 to Eagle Exp.Unit

NOTES: 1. Each Eagle unit contains setup software.

2. Connection cables must be ordered separately