Model LLG & LLD Pool and Spa Heater

Page 3

Notes:
1. An Underwriters' Laboratories listed vent cap is required to prevent downdraft and allow the heater to function properly

and safely.

2. Use approved roof jack.

2C. Site Location

WARNING

Improper installation or maintenance can
cause nausea or asphyxiation from carbon
monoxide in flue gases which could result in
severe injury, or death.

2C-1. Installation Information

Avoid placing the heater in locations where it can

cause damage by water or condensate leakage. If this is
not possible, provide a suitable drain pan to catch and
divert any leakage. The pan must not block natural
flow of air around the heater.

Locate the heater so the clearances from combus-

tible surfaces shown in Table 2 are met.

2C-2. Outdoor Installation

Laars Lite heaters can be installed in the low-

profile, grate top configuration (U.S.A. only) as
received from the factory, or with an optional high
wind vent cap/stack. Canadian units require a factory
approved vent cap.

Locate the heater in an open, unroofed area. Do

not install the heater under a deck. Do not locate the
heater below or adjacent to any doors, glass openings,
louvers, grills, etc., which connect in any way with an
inhabited area of a building, even though the access
might be through another structure (e.g., a garage or

Table 2. Minimum Heater Clearances From Combustible Surfaces

Figure 2. Indoor Installation Venting (USA), or Outdoor Shelter (Canada).

Table 1. Air Openings to Outside

Side of Heater

Indoor (Outdoor Shelter) Installation

Outdoors Installation

U.S.

Canada

U.S.

Canada

inch

cm

inch

cm

inch

cm

inch

cm

Blank

6

15.2

6

15.2

6

32

6

15.2

Rear

6

15.2

6

15.2

6

32

6

15.2

Piping

12

30.5

18

45.7

12

30.5

18

45.7

Top

44

111.7

44

111.7

Open Unroofed Area

Front

18

45.7

36

91.4

18

45.7

36

91.4

(

)

(

)

(

)

(

)

(

)

(

)

(

)

(

)

(

)

(

)

(

)

(

)

(

)

(

)

(

)

(

)

(

)

(

)

(

)

(

)

(

)

(

)

Required Net Free Open Area
for Combustion Air Openings

Direct from outside

Duct from outside

Model

in

2

(cm

2

)

in

2

(cm

2

)

125

32

(206)

64

(413)

175

44

(284)

88

(568)

250

63

(406)

126

(813)

325

82

(429)

164

(1058)

400

100

(645)

200

(1290)

Note: If using screens and/or louvers, compensate by adding 50%
additional area to each opening.