TOSHIBA

5.0

Operating the UPS

5.1

Operation Modes

5.1.3

Circuit-bypass mode

Power flow in circuit-bypass mode.
If the UPS unit is severely overloaded or develops an internal fault, the power flow

is automatically switched from the unit's main circuit to the bypass circuit mode.

Power flow through the bypass is shown in the above illustrations. This change-

over occurs automatically in approximately 4 milliseconds. The switching period

is not long enough to cause interruptions to occur in most UPS equipment loads.

The energy flow must be transferred manually from the UPS's bypass

circuit back to the inverter circuit after first correcting the fault. Toggle the

STOP/RUN switch (on the unit's front panel) first to STOP and then back to RUN.

This procedure resets the UPS and transfers back to inverter. During circuit-

bypass mode the AC-Input LED is ON, the On-Line LED is OFF, and the Fault

LED may be ON or OFF.(See Section 9.2 Panel Layout).

5.2

System Protection Features

UPS batteries

Bypass circuit

UPS

main

circuit

UPS

receptacles

(rear panel)

= power flow

-

5-15P

5-15R

Power

input plug

Fuse

Transformer

(Plus Series)

+

The schematic shown below depicts the electrical locations of the protection devices on

the UPS.

Input

Abnormal

Overcurrent

Low Battery

Level

Overheating

Current Limit

Overload

Overvoltage/

Undervoltage

Inverter

Rectifier/

Charger/

Chopper

+

Batteries

–

Fuse

Input

Transformer

(Plus Series)

Output

Output

5 - 2