Operating the UPS (Cont'd)

5.6

Battery Recharging
The graph below shows the typical voltage requirements for recharging the UPS unit's

batteries.

Model

Vmax.

Vmin.

Charge

600 VA / 600 VA Plus

68.2

48.0

0.4 (A)

800 VA / 800 VA Plus

68.2

48.0

0.4 (A)

1000 VA / 1000 VA Plus

68.2

48.0

0.4 (A)

1200 VA

68.2

48.0

0.4 (A)

Rated battery voltages

Period 1

Period 2

Period 3

Time

Current

Voltage

Vmax.

Vmin.

Battery

charge

voltage

Fully

charged

Discharge

shut-off point

Charging

current

0.4 amp (A)

0

0

The recharge process usually consists of three periods. During the first period, the

current is maintained at approximately 0.4 amperes. In the second period, the constant-

voltage control starts and the current gradually decreases as the batteries continue to

charge. In the third period, a slight current flows into the batteries to keep them fully

charged. After a complete discharge, a full recharge usually requires 24 hours (90%

recharge in 8 hours).

The chart depicted below shows the rated maximum and minimum battery voltages,

and the charge current for each of the sizes.