background image

69

4. In this case, we are accessing 32 words of global data, so set the bottom

portion of the MSTR instruction (“number of registers”) to 32. In the case
of MSTR global reads, this number cannot exceed 32 by definition.

5. Initiate the global read command by closing internal relay 1. The data

response will be seen in the MSTR Data Area (starting at register 40300).


15.6 MSTR Global Write Example

The following example demonstrates how to use the MSTR instruction to write
32 words of global data from a Modbus Plus master located at network address
1. Once written, any node on the Modbus Plus network will have access to this
global data. The same global data values will continue to be available until
another global data write occurs. Global data can only be cleared by
performing a global data write with a length of 0 words.

1. Set up a ladder logic program as shown in Figure 37.

2. Set the top portion of the MSTR Instruction to 40080. This will be the

starting address of the MSTR Control Block. Set the control block registers
to the following values:

Address Description Register

Value

40080

MSTR function (global write)

5

40081

Error code

Read Only

40082

Number of consecutive registers to write

32

3. Set the middle portion of the MSTR instruction to 40400. This will be the

starting address of the MSTR Data Area. This is the location of the data
that will be written to the master’s network global data.

Address Value

40400

Value to write to offset 0 in the master’s global data

40401

Value to write to offset 1 in the master’s global data

: :

40400+n Value to write to offset n in the master’s global data

: :

40431

Value to write to offset 31 in the master’s global data

4. In this case, we are writing 32 words of global data, so set the bottom

portion of the MSTR instruction (“number of registers”) to 32. In the case
of MSTR global writes, this number cannot exceed 32 by definition.

5. Initiate the global write command by closing internal relay 1. The data at

registers 40400-40431 will be written to the master’s (station address 1)
global data.