3. Group read and write registers together in the programmable pointer list

and access them with separate Modbus commands. The ETH-100 can
process read requests and write requests faster when they are grouped together
rather than the master having to issue multiple transactions to access disjoint
registers. This is especially true when the registers to be accessed are also
configured as ASD scan registers. Pointer registers can be accessed in any
combination of starting register and length. In the setup below, you would
optimize ETH-100 efficiency by having two Modbus transactions: one read
request with a length of 6 starting at register FC00, and one write request with a
length of 2 starting at register FC08.

Table 5: Grouping Read and Write Registers In The PPR List

Modbus Pointer Registers

(Also configured to be ASD READ

scan registers)

Modbus Pointer Registers

(Also configured to be ASD

WRITE scan registers)

Register

Points To…

Register

Points To…

FC00 FE03

FC08 FA02

FC01 FE06

FC09 FA01

FC02 FD01

FC0A

FC03 FE02

FC0B

FC04 FC91

FC0C

FC05 FE04

FC0D

FC06

FC0E

FC07

FC0F