4 user functions, In-service patching, User functions – Telect T3 User Manual

Page 13

Advertising
background image

Issue A Rev 2

108469

Telect, Inc.

4-1

I

N

-S

ERVICE

P

ATCHING

To temporarily connect an NE or DCS circuit to an alternate DCS or NE
circuit on the same or a different DNI-3 panel or DSX without disrupting
service, follow the steps below, using the Twist Lok Jacks (TLJs) on the
front of the appropriate DNI-3 panels and the following additional equip-
ment:

Four Mini-WECO patch cords (Mini-WECO plug at each end)

Two 75-ohm Mini-WECO terminating plugs

One dual bridging office repeater (BOR), or two single BORs

Step

Action

1.

Using one Mini-WECO patch cord:

a. Insert the plug of one end into BOR position 1, INPUT.

b. Insert the plug of the other end to the monitor TLJ at the first lo-

cation.

2.

Using a second Mini-WECO patch cord:

a. Insert the plug of one end into BOR position 1, OUTPUT.

b. Insert the plug of the other end into the IN TLJ at the second lo-

cation.

3.

Using a third Mini-WECO patch cord:

a. Insert the plug of one end into BOR position 2, INPUT.

b. Insert the plug of the other end into the monitor TLJ at the sec-

ond location.

4

User Functions