2 installation, Installation considerations, Location and space – Telect T3 User Manual

Page 7: Installation, Nstallation, Onsiderations

Advertising
background image

Issue A Rev 2

108469

Telect, Inc.

2-1

I

NSTALLATION

C

ONSIDERATIONS

Location and Space

The DNI-3 panel mounts flush into both unequal-flange and equal-flange
(EIA or WECO) 23" (58.4 cm) network bays. The primary limiting factor
of a DNI-3 rack configuration is the number of cables a network bay can
accommodate. (The DNI can accommodate 1280 coax cables.)

NOTE

Telect recommends a maximum of 14 DNI-3 panels per bay, regardless of
bay capacity, for easy access and adequate room for cable routing.

Here are the DNI-3 space requirements:

DCS

Terminations

Panels

Total Cables

Cable Space

Needed per Side

of Bay (in.

2

)

EIA Bay Spaces

Required

1–32

1

128

1.64

3

33–64

2

256

3.28

6

65–96

3

384

4.92

9

97–128

4

512

6.55

12

129–160

5

640

8.19

15

161–192

6

768

9.83

18

193–224

7

896

11.47

21

225–256

8

1024

13.11

24

257–288

9

1152

14.75

27

289–320

10

1280

16.38

30

321–352

11

1408

18.02

33

353–384

12

1536

19.66

36

2

Installation