2 multi-function input terminal, 3 -10v power supply – Toshiba ETB003Z User Manual

Page 12

Advertising
background image

E6581339⑤

11

3.2 Multi-function input terminal

Four output terminals can be added. Function is similar to that of the input terminals of
the inverter, so refer to the inverter instruction manual.

Parameter

Title

Function

Adjustment range

Default setting

f119

Input terminal selection 9 (LI1)

0 - 135

0

f120

Input terminal selection 10 (LI2)

0 - 135

0

f121

Input terminal selection 11 (LI3)

0 - 135

0

f122

Input terminal selection 12 (LI4)

0 - 135

0

f144

*

Input terminal 5~12 response time selection

2 - 200ms

8

* VF-PS1 does not have this parameter.

Monitor

Refer to the description on status monitor mode of inverter’s instruction manual.
The input terminal status can be monitored by the input terminal status parameter
(fe06), and the parameter can be monitor by the serial communication.

fe06

bit

No. 15

14 13 12

11

10

9 8 7 6 5 4 3 2 1 0

Symbol

LI8

LI7

LI6

LI5

LI4

LI3

LI2

LI1

S4

S3

S2

S1

RES

ST

R F

Note: The LI5 ~ LI8 are the terminal function of the expansion IO card option 2.

3.3 -10V power supply

The frequency command can be input from RX terminal with pulse and negative voltage
using N10(-10V) and PP(+10V) power.

Potentio meter
Center position: 0V command
Pulse side position: +10V command
Negative side position: -10V command

The recommended wiring cable length is
less than 1.5m with shielded cable.

Option Terminal

PP (+10)

RX

N10 (-10V)

2k ohm

Inverter Terminal