2.2 Wiring

When conducting wiring, follow the instructions below.
• Use shield wire for control signal line and ground the unit with shield wire.

(Use twisted pair shield cable for wiring of the analog monitor output.)

• Applicable wire size ...................................... TB1: 0.2 to 2.5 mm

2

TB2, TB3: 0.2 to 1.5mm

2

• The wire length of peel off the end ............... TB1: About 5mm

TB2, TB3: About 7mm

• Using screwdriver .........................................TB1: The blade tip has 0.6mm thickness

and 3.5mm width.

TB2, TB3: The blade tip has 0.4mm thickness

and 2.5mm width.

• Tightening torque of the terminal block ........ TB1: 0.5 to 0.6 N

m

TB2, TB3: 0.22 to 0.25 N

m

• Never bind the signal line and main circuit connection wire together.