• Purchaser piping and instrumentation diagram including suction and recycle

pipe size and schedule

• Anti-surge control (recycle) valve and specification sheet, unless included in

Solar's scope

• Suction and discharge gas temperature signal (100-ohm platinum resistance

temperature devices (RTDs) preferred)

Typical system scope includes the following:

• Engineering to determine the optimum control algorithms
• Control software programmed and tested for the selected gas compressor

staging

• Engineering to specify the anti-surge control valve and accessories, including

valve performance evaluation over the gas compressor performance map at
varying valve positions

• Engineering to specify the flow meter type and size
• Automatic override of manual control mode
• Evaluation of user piping and instrumentation diagram
• Documentation, including all surge control calculations and program constants
• Gas compressor flow versus differential pressure control with suction pressure

and temperature compensation

• Speed setpoint decoupling
• Surge detection with step valve opening
• On-screen, real-time graphic displays
• On-screen, real-time control parameter setting
• All surge control parameters are available for remote monitoring via serial link

11.1.5 Anti-Surge

Recycle

Valve

When included in Solar’s scope of supply, the anti-surge recycle valve is supplied as a
complete and functionally tested assembly, shipped separately for field installation. The
assembly includes the valve and the following accessories and features:

• Spring-return, diaphragm-type, pneumatic actuator
• Position transmitter with valve fully open and fully close relay outputs and 4-to-

20 mA proportional to percentage closed

• Pressure regulator
• 3-way 24-VDC solenoid valve
• Electropneumatic valve positioner
• ½-in. NPT actuator pressure port
• Carbon steel body per ASTM A352
• Interconnecting 316L stainless steel tubing and compression-type fittings
• Temperature Limits:

− Process gas:

-

6.7

o

to 218°C (20 to 425°F)

− Ambient:

-

28.9

o

to 60°C (

-

20 to 140°F)

The assembly requires clean, dry regulated air or natural gas, 552 to 862 kPag (80 to 125
psig), -28.9

o

to 60°C (-20

o

to 140°F), dew point -40°C (-40°F)

Successful operation of the anti-surge control system is dependent on correct valve
selection. The following anti-surge recycle valve is selected based on the application data