Specifications, Hardwired models) – Tripp Lite APS PowerVerter User Manual

Page 15

Advertising
background image

15

Specifications

(Hardwired Models)

HARDWIRED MODELS:

APS 2012

APS2424

Weight:

38.0 lbs.

41.0 lbs.

INVERTER
Continuous power (@ 20° C):

2000 W

2400 W

Surge power (5 seconds):

4000 W

4800 W

Efficiency (Full Load):

90%

90%

Minimum DC Fuse Rating:

500A

300A

DC Input Current @ Nominal V DC

Full Load

192 A

112 A

No Load

2.5 A*

1.5 A*

Nominal Input Volts:

12 VDC

24 VDC

DC Input Voltage Range:

10-15 VDC

20-30 VDC

Nominal Output Volts:

120 VAC ±5%

120 VAC ±5%

Nominal Output Frequency:

60 Hz ±.3%

60 Hz ±.3%

BATTERY CHARGER
Charging Capacity DC:

60 A

30 A

Maximum Cable Length

1 ft.

3 ft.

Acceptance Volts VDC:

Selectable

Selectable

14.4 V**/14.2 V Wet**/Gel

28.8 V**/28.4 V Wet**/Gel

Float Volts VDC (w/gel):

13.3 V (13.6 V)

26.6 V (27.2 V)

Input Voltage AC:

120 V

120 V

Input Current AC:

16 A

16 A

LINE VAC OPERATION
Minimum Input AC Volts:

Selectable 75**,85, 95, or 105 VAC Selectable 75**,85, 95, or 105 VAC

Maximum Input AC Volts
(Continuous, Charger at Maximum):

Selectable 135** or 145 VAC

Selectable 135** or 145 VAC

Maximum Input Current
(Continuous, Charger at Maximum):

32 A

36 A

Input Frequency:

60 Hz ±10%

60 Hz ±10%

Maximum Output AC (Continuous)

16.7 A

20 A

Automatic Transfer Time:

4-6 ms

4-6 ms

HARDWIRED MODELS (Cont.):

APS 2448

APS3636VR

Weight:

38.0 lbs.

56.9 lbs.

INVERTER
Continuous power (@ 20° C):

2400 W

3600 W

Surge power (5 seconds):

4800 W

7200 W

Efficiency (Full Load):

90%

89%

Minimum DC Fuse Rating:

300A

300A

DC Input Current @ Nominal V DC

Full Load

56 A

114 A

No Load

1.5 A*

1.7 A*

Nominal Input Volts:

48 VDC

36 VDC

DC Input Voltage Range:

40-60 VDC

30-45 VDC

Nominal Output Volts:

120 VAC ±5%

120 VAC ±5%

Nominal Output Frequency:

60 Hz ±.3%

60 Hz ±.3%

BATTERY CHARGER
Charging Capacity DC:

15 A

30 A

Maximum Cable Length

12 ft.

4.5 ft.

Acceptance Volts VDC:

Selectable

Selectable

57.6 V**/56.8 V Wet**/Gel

43.2 V**/42.6 V Wet**/Gel

Float Volts VDC (w/gel):

53.2 V (54.4 V)

39.9 V (40.8 V)

Input Voltage AC:

120 V

120 V

Input Current AC:

16 A

24 A

LINE VAC OPERATION
Minimum Input AC Volts:

Selectable 75**,85, 95, or 105 VAC Selectable 75**,85, 95, or 105 VAC

Maximum Input AC Volts
(Continuous, Charger at Maximum):

Selectable 135** or 145 VAC

Selectable 135** or 145 VAC

Maximum Input Current
(Continuous, Charger at Maximum):

33 A

54 A***

Input Frequency:

60 Hz ±10%

60 Hz ±10%

Maximum Output AC (Continuous)

20 A

30 A

Automatic Transfer Time:

4-6 ms

4-6 ms

*Load sense can reduce this to 1/30 of the listed current. **Factory default setting. ***When AVR is boosting incoming current.

200103046 120V APS MV-cabinetEn-Sp 93-1911.qxd 7/2/01 10:18 AM Page 15