2 external output function – MITSUBISHI ELECTRIC GB-50A User Manual

Page 10

Advertising
background image

9

(A) Level signal

When the level signal is selected, the operation (only ON/OFF operation) for the central controller and

the local remote controller are prohibited (except during normal operation).

When the emergency stop/normal operation signal is selected, the status will be changed from normal

operation to emergency stop when the external input signal contact turns OFF to ON, and will be
changed from emergency stop to normal operation when external input signal contact turns ON to OFF.
Emergency stop signal will bring the air conditioners to stop, and canceling the emergency stop will not
automatically restart these units. To go back to the previous operation status, they must be manually
turned back on.

When ON/OFF input signal is selected, the status will be changed from OFF to ON when the external

input signal contact turns OFF to ON.


(B) Pulse signal

Even if the ON signal is input during ON, the status will remain at the ON status.

When the local remote controller is prohibited, the ON/OFF operation, operation mode selection and

temperature setting from the local remote controller is prohibited.

Set the pulse width (contact ON time) to 0.5 to 1.0 second.


4-2 External output function

(1) The function of external output

●The “ON” signal is output when one or more air conditioner are in the ON operation.
●The “Malfunction” signal is output when one or more air conditioner malfunctions.

(2) Specification of external output interface

CN2

Lead wire

Description of each terminal

No. 1

Green

Common (0V)

No. 2

Black

ON/OFF

No. 3

Brown

Malfunction/Normal