4 external input/output function, 1 external input function – MITSUBISHI ELECTRIC GB-50A User Manual

Page 9

Advertising
background image

8

*External signal input requires the external I/O adapter (Model: PAC-YG10HA) sold separately.

4-1 External input function

(1) The function of external input
• Emergency stop/normal operation, ON/OFF, local remote control prohibit/permit can be controlled for

conditioners being controlled with a non-voltage contact signal input from an external input source.
(the dip switches)

• The condition of external input signal is displayed on the operation setting screen for each group.

Table 4-1. Function settings of external input

No.

Function of external input signal

Remarks

1

External input signal not used

-------------------------------------------------------------

2

Perform emergency stop with level signal

During emergency stop, only ON/OFF of the
central controller and local remote controller’s
operation will be prohibit.

3

Perform ON/OFF operation with level signal

Only the ON/OFF operation of the central controller
and the local remote controller will be prohibit.

4

Perform ON/OFF operation, prohibit/permit
operation with pulse signal

Set the pulse width while the contact is ON to 0.5 to
1.0 second.

*Settings for these functions can be set with the Initial Setting Web or Initial Setting Tool.

(2) Level signal and pulse signal

(3) Specification of external input interface

CN2 Lead

Wire

Emergency stop/normal

level signal

ON/OFF level signal

ON/OFF, prohibit/permit

pulse signal

No.5 Orange Emergency

stop/normal

input

ON/OFF input

ON input

No.6

Yellow

Not used

Not used

OFF input

No.7

Blue

Not used

Not used

Local remote controller

prohibit input

No.8

Gray

Not used

Not used

Local remote controller

permit input

No.9

Red

Common (DC12V or DC24V)