CU111 connection

6.Computer Link (RS485) interface

(1)Computer Link (RS485) signal name and pin assignment

(2)Computer Link (RS485) interface connection

Short between RXA(Pin No.3) and TRM(Pin No.4) for termination of one-to-one configuration
at CU111. Refer to the next page.
Note

¬ Use the shielded twisted-paired cable for noise immunity and ground the cable shield at

one end.

- Connect SG (Signal Ground) each other.
® The adapter does not have the frame ground (FG) terminal, so please ground directly.
¯ Please make the program transmitting again.

Pin No. Signal Name

Function

1

TXA

CU111

RS485 (In phase signal)

2

TXB

CU111

RS485 (Reverse signal)

3

RXA

CU111

RS485 (In phase signal)

4

TRM

Termination

5

RXB

CU111

RS485 (Reverse signal)

6

SG

Signal Ground

TXA

1

TXB

2

RXA

3

TRM

4

RXB

5

SG

6

R

Sheilded
twisted-paired cable

RS232C/RS485

Multi-drop adapter

CU111

Host Equipment

RS485 Interface

1

TXA

RXA

RXD

TXD

2

TXB

RXB

3

TXA

RXA

4

TXD

RXD

TRM

5

TXB

RXB

6

SG

SG