MICROELECTRONIC HEAT PUMP THERMOSTAT

INSTALLER SETUP

NOTE:

For most applications, the thermostat factory
settings do not need changing. Review the
Factory Setting column in Table 2 and if no
changes are necessary, go to the Installer
System-Test section.

Use the Installer Setup to customize the thermostat to
specific systems. Some of the options include temperature
display, changeover, minimum equipment on time and
minimum off time. Installer Setup numbers are listed in
Table 2. It includes all the configuration options and the
factory-settings available for the T8511.

IMPORTANT

The Installer Setup must be set correctly for the
HVAC equipment, thermostat and subbase to
operate properly.

A combination of key presses are required to use the
Installer Setup feature:

1. To enter the Installer Setup, press and hold the

Information i key and the increase

and

decrease

keys until the first number displays. All

display segments appear for approximately three
seconds before the number displays. See Fig. 11
and 12.

2. To advance to the next Installer Setup, press the

Information i key.

3. To change a setting, press the increase

or

decrease

key.

4. To exit the Installer Setup, press and hold the

Information i key until the display returns to
normal (approximately three seconds). The display
scrolls the numbers backward to get to the normal
display. The Installer Setup is automatically exited if
no key presses are made for five minutes.

Fig. 11. Display of all LCD segments.

Fig. 12. Display of installer setup and setting.

NOTE:

Only configurable numbers are shown.

Em HeatOffCool Auto Only

Heat Cool

OnAuto

System

Fan

Room

Outdoor

Em Ht Temporary Setting

Wait

%Humid

Aux Ht

Remote

Repl

Batt

M4844

Table 2. Thermostat Installer Setup Options.

M10105A

INSTALLER SETUP
NUMBER DISPLAY
(COLUMN 2 OF TABLE 2)

FACTORY SETTING OR
OTHER CHOICE DISPLAY
(COLUMN 3 OR 5 OF TABLE 2)

a

The cycle rate for the last stage of heat is adjustable with 6 as the factory setting.

(continued)

Installer Setup

Number

(Press

i

key

Factory Setting

Other Choices

(Press

or

key to change)

Actual

Select

to change)

Display

Description

Display

Description

Setting

Not used.

01 thru 04

Heating cycle 05

03

Stage 2.

03, 06

03—3 cph used for stage 1

rate.

06

Not used.

or 09

heat pump systems.

07

09

Emergency heat.

06—6 cph used for

conventional systems.

09—9 cph used for electric

heat systems.

Not used.

08 thru 11

Changeover
(T8511G only).

12

01

Manual changeover.

00, 02

00—Automatic changeover.
02—Automatic changeover

only

Not used.

13

Degree
temperature
display.

14

00

Temperature is
displayed in °F.

01

Temperature is displayed
in °C

Not used.

15 thru 18