VENT INSTALLATION

WARNING:

This boiler shall not be connected to any portion of a mechanical

draft system operating under positive pressure.

1. The vent pipe must slope upward from the boiler not less than 1/4 inch for every 1 foot

to the vent terminal.

2. Horizontal portions of the venting system shall be supported rigidly every 5 feet and

at elbows. No portion of the vent pipe should have dips or sags.

3. This boiler series is classified as a Category 1 appliance and the vent installation shall

be in accordance with Part 7 & 11 of the latest revision of the National Fuel Gas Code or

applicable provisions of the local building codes.

4. Inspect chimney to make certain it is constructed according to National Board of Fire

Underwriters.

5. Attach draft hood to flue collector at rear of boiler, (See figure 7, below), with sheet

metal screw(s) through hole(s) provided. The vent or vent collector shall be Type B or metal

pipe having resistance to heat and corrosion not less than that of galvanized sheet steel or

aluminum not less than 0.016 inch thick (No. 28 GA).

6. Connect flue pipe same as draft hood to chimney. Bolt or screw joints together to avoid

sag. Flue pipe should not extend beyond inside wall of chimney. Do not install manual

damper in flue pipe or reduce size of flue outlet except as provided by the latest revision of

ANSI Z223.1. Protect combustible ceiling and walls near flue pipe with fireproof insulation.

Where two or more appliances vent into a common flue, the area of the common flue must

be at least equal to the area of the largest flue plus 50 percent of the areas of each additional

flue.

PAGE 7

WARNING:

ALL

INSTALLATIONS OF BOILERS

AND VENTING SHOULD BE

DONE ONLY BY A QUALIFIED

EXPERT AND IN ACCORDANCE

WITH THE APPROPRIATE UTICA

BOILERS MANUAL. INSTALLING

OR VENTING A BOILER OR ANY

OTHER GAS APPLIANCE WITH

IMPROPER METHODS OR

MATERIALS MAY RESULT IN

SERIOUS INJURY OR DEATH

DUE

TO

FIRE

OR

TO

ASPHYXIATION

FROM

POISONOUS GASES SUCH AS

CARBON MONOXIDE WHICH IS

ODORLESS AND INVISIBLE.