UNIREX Pump User Manual

Page 22

Advertising
background image

MARK 3 USER INSTRUCTIONS ENGLISH 71569102 08-06

Page 22 of 68

flowserve.com

Mark 3 design (old)

If an adjustment is necessary, the adjuster nut

[6576] is used to move the footpiece up or down.

g) The spacer coupling gap is verified.

h) The parallel and angular vertical alignment is

made by shimming under the motor.

i) The motor feet holes are again centered on the

motor mounting studs using the centering nut. At

this point the centering nut is removed and

replaced with a standard nut. This gives

maximum potential mobility for the motor to be

horizontally moved during final, field alignment.

All four motor feet are tightened down.

j) The pump and motor shafts are then aligned

horizontally, both parallel and angular, by moving

the pump to the fixed motor. The pump feet are

tightened down.

k) Both horizontal and vertical alignment is again

final checked as is the coupling spacer gap.

See section 4.8,

Final shaft alignment

.

4.5.2 In-Line initial alignment procedure

The factory alignment proceed procedure ensures

that the unit may be aligned in the field. The initial

alignment is no more than 0.38 mm (0.015 in.)

parallel, and 0.0025 mm/mm (0.0025 in./in.) angular

misalignment.

The Mark 3 In-Line incorporates motor alignment

capabilities. Parallel alignment is achieved by

moving the motor adapter and motor as an assembly

relative to the power end. Four adjustment screws

(as shown in figures 4-7 and 4-8) allow for precise

changes in parallel alignment. Angular alignment is

controlled by machining tolerances, but cannot

prevent uneven cover gasket compression.

a) Check angular alignment. Additional torque may

be applied to the appropriate casing bolts to

correct angularity.

b) Check parallel alignment within a plane defined by

the adjusters at opposite corners of the motor

adapter. To make corrections, the motor adapter

nuts [6580.3] must be slightly loosened to allow the

motor adapter to move. All adjusters except for the

one in the desired direction of motor movement

should be loosened during adjustment. Tighten the

adjuster slowly against the stud until desired

alignment numbers are reached.

c) Check parallel alignment within a plane 90

degrees from the first. Corrections are made as

described in the previous step.

d) Several iterations between planes may be

necessary. Tighten all fasteners and recheck

alignment.

Figure 4-7

Figure 4-8

4.6 Piping

Protective covers are fitted to both the

suction and discharge flanges of the casing and must

be removed prior to connecting the pump to any pipes.

4.6.1 Suction and discharge piping

All piping must be independently supported, accurately

aligned and preferably connected to the pump by a

short length of flexible piping. The pump should not

have to support the weight of the pipe or compensate

for misalignment. It should be possible to install suction

and discharge bolts through mating flanges without

pulling or prying either of the flanges. All piping must be

tight. Pumps may air-bind if air is allowed to leak into

the piping. If the pump flange(s) have tapped holes,

select flange fasteners with thread engagement at least

equal to the fastener diameter but that do not bottom

out in the tapped holes before the joint is tight.

4.6.2 Suction piping

To avoid NPSH and suction problems, suction piping

must be at least as large as the pump suction

connection. Never use pipe or fittings on the suction

that are smaller in diameter than the pump suction size.

Advertising