- 17 -

Fig. 6 Liquid Filter Fig.7 Liquid Indicator

Fig. 8 Temperature Controller (4.25”L X 3.75D X 4.25”H)

2. Evaporator Unit Installation

1) WM-25~85SFCH evaporator units can be installed outside a wine cellar. It

shall not be exposed to temperatures higher than 85 °F.

2) Air supply shall be unobstructed minimum 12” for a direct blow installation;

leave 2” clearance for a deflector installation; air return shall be unobstructed
minimum 6”.

3) Secure the ducts with conduits to the cellar exterior walls and make sure they

are not curled, twisted, bent and clogged.

4) There is a gravity drain system used, so the unit shall be installed level or with

a slight slope downward the drain connection and the drain line shall be
installed slope down toward the drain. If rise-up is needed, a condensation
pump must be used.

3. Condensing Unit Installation

CAUTION:
Low ambient condition kit is required if the installation area will be below
50

°

F.

If the condensing unit is equipped with a low ambient condition kit,

do not turn on the compressor until the condensing unit has been powered
for minimum 12 hours.

1) Place the condensing units WM-250~850SCU in a properly ventilated

location. If it is not, heat exhausted by the condensing unit will build up and
the cooling system will not operate properly.