Vinotemp WINE-MATE 250SCU User Manual

Page 5

Advertising
background image

- 4 -

g. Low suction pressure and low head pressure
High superheat and low subcooling
h. Low suction pressure and low to normal head pressure
High superheat and high subcooling

i.

Low suction pressure and low head pressure

Low subcooling
j.

Low suction pressure and low head pressure

Low superheat and low subcooling
k. Low suction pressure and low to normal head pressure
High superheat and normal to high subcooling
l.

Low suction pressure and normal head pressure

High superheat and normal subcooling
m. Low suction pressure and high head pressure
High superheat and high subcooling
n. Low suction pressure and high head pressure
High superheat and high subcooling
o. low to normal suction pressure and high head pressure
High to normal superheat and high subcooling

g. Undercharge

h. Liquid line restricted after

receiver, solenoid valve
restricted

i.

Suction line restricted


j. Air restricted at evaporator,

evaporator iced

k. Evaporator

restricted


l.

Expansion valve restricted


m. Both evaporator and condenser

restricted

n. Liquid line restricted before

receiver

o. Condenser

restricted


7.

Use of the adjustable pressure control (if applicable for pump-down)


Suction pressure setting: Cut out=5 psig; Cut in=25 psig; Differential=20 psig
Head pressure setting: Cut out=230 psig; Cut in=150 psig; Differential=80 psig

It may need to adjust the setting in the field to get the right cycle time.

A. Single Control

Fig. 3 Single Adjustable Pressure Control





Advertising
This manual is related to the following products: