Westinghouse Teco MA7200 Plus User Manual

Page 17

Advertising
background image

MA7200 PLUS Inverter 1 to 2 HP PID Fan and Pump Quick Start Manual
__________________________________________________________________

________________________________________________________________

TECO – Westinghouse Motor Company

17






• To further cover the PID Sleep function, the following is an example of the various

parameter settings that could be used. In this example the system will have the following
specifications:

-

Max. Pump Motor Speed : 3600 RPM.

-

Set Point: 150 PSI.

-

Feedback Transducer Range: 0 – 200 PSI.

-

Pump System Sleep Level: 2160RPM or 60% of max. speed set by

(P21-01=060.00). Sleep Level Delay Time: 10 sec. set by (P2-02=010.0 ).

-

Pump System Wakeup Level: 100 PSI set by (P2-03=0100). Wakeup Time: 5 sec.
set by (P2-04=005.0).

• Referring

to

Step 9, set the engineering units to PSI (P1-01=02) and then the range to 200

(P1-02=0200).

• On the following pages the keypad navigation sequence is shown in setting the PID

parameters.

NOTE: The inverter must be in the Stop mode in order to turn on the sleep function.




Advertising