MA7200 PLUS Inverter 1 to 2 HP PID Fan and Pump Quick Start Manual
__________________________________________________________________

________________________________________________________________

TECO – Westinghouse Motor Company

8

Step 7

– Setting Minimum Speed in Pump Applications

(NOTE: In the case of a fan application skip this step and go to Step 8)

• In the case of pump applications it is normally required to limit the minimum speed that the

pump will operate regardless of the input speed command. The pump minimum speed is
usually specified either by the pump manufacturer or the application. Once this value has
been established, the minimum output frequency of the inverter and thus the minimum
motor (pump) speed can be set by parameter Cn-19. This parameter sets the minimum
inverter frequency output, and thus a minimum motor (pump) speed to a percentage of the
maximum output command frequency.

• The following is an example of setting the minimum motor (pump) speed to 1800 RPM,

which is 50% of the maximum pump speed, 3600 RPM.

PRGM

DRIVE

DSPL

Cn-01

key 3 times

Input Voltage

1 - Press the

2 - Press the

4 - Press the

key

key

An – 01 -

Freq. Cmd. 1

Cn-19 = 000%

EDIT

ENTER

key to save.

6 - Press the

Entry Accepted

2 Seconds

PRGM

DRIVE

7 - Press the

key to return to the main display.

Flashing

EDIT

ENTER

Flashing

To set parameter Cn-19 = 050%

(Minimum pump speed )

Keypad Steps

Resulting Display

3 - Press the

key until the display shows

Cn-19

Freq Cmd Low Bound

Freq Cmd Low Bound

RESET

key twice; then the

key 5 times

5 - Press the

Cn-19 = 050%

Flashing

Freq Cmd Low Bound

Cn-19 = 050%

Freq Cmd Low Bound