Operation menu, Operation menu prompts/description – Watlow Electric Micro-Based Autotuning Control SERIES 980/985 User Manual

Page 28

Advertising
background image

Chart 3 -
Operation Menu

Prompts and
Descriptions.

Dead Band: Enter the Dead Band between the heating and cooling functions

adjustable from ± 99°F/± 55°C. The default is 0°. Appears when Ot2 = CL.

Alarm Low: Represents the low process alarm or low deviation alarm.

Displayed only when 0t2 parameter is AL.

Alarm High: Represents the high process alarm or high deviation
alarm. Displayed only when Ot2 parameter is AL.

Calibration Offset. The range is ±99°F/±55°C. The default is 0°.
Calibration Offset adds or subtracts degrees from the input signal.

Auto-Tune. The range of this parameter is 0-3, off = 0, slow = 1,

medium = 2, and fast = 3. A value other than 0 initiates the auto-tune.

Local-Remote: Selects a local or remote set point for the Series 980/985.
Local set point is adjustable directly from the 980/985, while remote can only

be changed from an external device. The signal must be within O-5V or 4-
20mA process input. This parameter appears if the LOC parameter = 0, 1 or 2,
and

rSP = 0-5 or 420.

If L-r = the remote set point is displayed in place of the

internal set point.

Use this page as a master copy for your Series 980/985. Operation Parameters.

Do not enter any values here: make photocopies instead.

1

Operation Parameters

Value

Range

Factory Default

SP2

rL to rH

Same as primary set point.

Pbl

0 to 999°F/0 to 555°C or

25°F/l3°C (3 or 4 digit)

0 to 99.9°F/0 to 55.5°C
0=ON/OFF control

with 3°F or 1.7°C
switching differential.

0.3°F or 0.17°C

for 0.10 units.

Pb2

Same as Pb1

. Only appears

if

0°F/0°C

(3

or

4 digit)

Ht/CL or CL/Ht

operation.

rE1

0.00 to 9.99 repeats/min.

0.00 repeats/min.

0.00 = No Reset Action

rE2

Same as rE1. Only appears if

0.00 repeats/min.

Ht/CL or CL/Ht operation.

Will not appear if Pb2 = 0.

rA1

0.00 to 9.99 min.

0.00 min.

0.00 = No Rate Action

rA2

Same as rA1. Only appears

0.00 min.

if Ht/CL or CL/Ht operation.

Will not appear if Pb2 = 0.

AL0 -

Deviation dE

-99° to (3 digit display)

-99°

-999° to 0° (4 digit display)

-999°

Process Pr

rL to AH1

rL

AHI -

Deviation dE

0 °

to 99° (3 digit display)

99°

0 °

to 999° (4 digit display)

999°

Process Pr

AL0 to

rH

Ctl

1 to 60 seconds

5 seconds

Ct2

1 to 60 seconds

5 seconds

Appears if Ht/CL or CL/Ht

Will not appear if PB2 = 0

db ±99°F/±55°C.

0

Appears if Ht/CL or CL/Ht

CAL

±99°F/±55°C

0

AUt

0-3

0

Appears if Ot1 = Ht.

L-r

L or r.
Appears if rSP = 0-5 or 420.

2 8 WATLOW Series 980/985 User’s Manual Setup, Chapter 4