Installing the Oil Tank and Supply System

Fuel supply level with or above burner –

SK8745

Figure 7. – Mounting Burner in Appliance

Tilt down 2

o

If space between burner

air tube and opening
exceeds 1/2 inch, pack
burner opening with ce-
ramic fiber refractory.

Figure 8. – Inside Tank Gravity Feed System

Figure 9. – Outside Buried Tank-Lift System

NOTICE

To further protect the fuel supply sys-

tem and reduce nozzle orifi ce plugging with fi ring rates
below 0.75 gph, a dual fi ltration system can be installed.
This typically consists of a 50 micron primary fi lter,
located near the fuel tank and a secondary fi lter rated for
at least 10 microns located near the burner.

Never use Tefl on tape on fuel oil fi ttings.
Tape fragments can lodge in fuel line compo-
nents and fuel unit, damaging the equipment
and preventing proper operation.
Use oil-resistant pipe sealant compounds.

y
y

y

Damage to the pump could cause impaired

burner operation, oil leakage and appliance
soot-up.

Do Not Use Tef on Tape

!

!

CAUTION

Oil Leak and Fire Hazard

WARNING

!

Install the oil tank following applicable stan-

dards in the U.S. by referring to the latest
edition of NFPA 31 or CSA-B139 & CSA-B140
in Canada, and all authorities having jurisdic-
tion.

Note: to determine the proper fuel line size, refer

to the fuel pump manufacturer’s instructions pro-
vided with the burner. Refer to Figure 8 or Figure 9
for typical installation layouts.


Fuel Line Valves and Filter

Install two high quality, oil duty rated, fusible

handle design shutoff valves in accessible loca-
tions on the oil supply line. Locate one close to the
tank and the other close to the burner, upstream of
the fi lter for service access.

Install a generous capacity fi lter inside the building

between the fuel tank shutoff valve and the burner,
locating both the fi lter and the valve close to the
burner for ease of servicing. Filter should be rated
for 50 microns or less.

The burner is shipped without the by-pass plug
installed.
Install the by-pass plug in two-pipe oil supply
systems ONLY.

y

y

Failure to comply could cause Immediate pump

seal failure, pressurized oil leakage and the
potential for a fi re and injury hazard.

WARNING

!

Do Not Install By-pass Plug

with 1-Pipe System