Burner controls, Figure 10. – typical burner wiring – Weil-McLain UO-3 CV User Manual

Page 18

Advertising
background image

6104BAFG R0



Page 17

61351

7. RECYCLE. If the fl ame is lost while the burner is

fi ring, the control shuts down the burner, enters a 60
second recycle delay, and then repeats the above
ignition sequence. If fl ame is lost three times in a
row, the control locks out to prevent cycling with
repetitious fl ame loss due to poor combustion.

8. BURNER MOT OR-OFF DELAY. The fuel valve

is closed and the burner motor is kept on for the
selected motor-off delay time before the control re-
turns the burner to standby.

Typical Burner Wiring & Burner Sequence of Operation for R7184P Control.

Refer to the appliance manufacturer’s wiring diagram for actual specifi cations.

1. STANDBY. The burner is idle, waiting for a call for

heat. When a call for heat is initiated, there is a 3-
10 second delay while the control performs a safe
start check.

2. VALVE-ON DELAY. The ignition and motor are

turned on for a 15 second valve-on delay.

3. TRIAL FOR IGNITION (TFI). The fuel valve is

opened. A fl ame should be established within the
15 second lockout time.

4. LOCKOUT. If fl ame is not sensed by the end of

the TFI, the control shuts down on safety lockout
and must be manually reset. If the control locks out
three times in a row, the control enters restricted
lockout.

5. IGNITION CARRYOVER. Once fl ame is estab-

lished, the ignition remains on for 10 seconds to
ensure fl ame stability before turning off. If the con-
trol is wired for intermittent duty ignition, the ignition
unit stays on the entire time the motor is running.

6. RUN. The burner runs until the call for heat is sati-

fi ed. The burner is then sent to burner motor off
delay, if applicable, or it is shut down and sent to
standby.

Feature

Interrupted

ignition

Limited reset,

Limited recycle

Diagnostic LED,

cad cell indicator

Valve-on

delay

Burner motor

off delay

Alarm Con-

tacts

R7184A

YES

YES

YES

R7184B

YES

YES

YES

YES

R7184P

YES

YES

YES

YES

YES

Optional

Control System Features

Figure 10. – Typical Burner Wiring

Burner Controls