MAINTENANCE SCHEDULES

USE AND MAINTENANCE
SHALL BE IN ACCORDANCE
WITH THE STANDARD FOR
VENTILATION CONTROL
AND FIRE PROTECTION OF
COMMERCIAL COOKING
OPERATIONS
, N.F.P.A 17A
& N.F.P.A. 96 (current
editions).

DANGER

Fire Hazard

FAILURE TO PROPERLY
CLEAN AND MAINTAIN THIS
EQUIPMENT CAN
CAUSE A FIRE. AN
UNCONTROLLED FIRE CAN
CAUSE SERIOUS INJURY,
DEATH AND/OR PROPERTY
LOSS.


NOTE: A signed and dated
VENTILATOR HOOD
MAINTENANCE LOG must
be maintained on the
premises, and shall be
available for inspection by the
authority having jurisdiction.
See pages 26 & 27.


IMPORTANT: Parts used
for the Ansul® fire
suppression system are not
serviceable by the owner /
operator.
Procedures for
servicing fire suppression
equipment are described in:
ANSUL® R-102 SYSTEM
DESIGN, INSTALLATION,
RECHARGE AND
MAINTENANCE MANUAL
(Ansul® #418087-05).

1. 6-MONTH MAINTENANCE (MUST BE PERFORMED BY AN
AUTHORIZED ANSUL® DISTRIBUTOR ONLY)
:

a. Inspect and test total operation including FIRE DAMPER and
all SAFETY INTERLOCKS.

b. All FIRE SUPPRESSION SYSTEM actuation components
including MANUAL PULL STATION and any REMOTE
MANUAL PULL STATION must be inspected for proper
operation in accordance with the maintenance schedule
published in ANSUL® R-102 SYSTEM DESIGN,
INSTALLATION, RECHARGE AND MAINTENANCE MANUAL
(Ansul® #418087-05).

c. The FIRE SUPPRESSION SYSTEM FUSIBLE LINKS must be
inspected. NOZZLES and MANUAL PULL STATION must be
cleaned in accordance with ANSUL® R-102 SYSTEM
DESIGN, INSTALLATION, RECHARGE AND MAINTENANCE
MANUAL
(Ansul® #418087-05).

d. The FIRE SUPPRESSION AGENT TANK, PIPING and
FLEXIBLE TUBING must be INSPECTED.

2. 12-YEAR MAINTENANCE: (MUST BE PERFORMED BY AN
AUTHORIZED ANSUL® DISTRIBUTOR ONLY)
:

a. The FIRE SUPPRESSION AGENT TANK and ¼” FLEX HOSE
must be HYDROSTATICALLY TESTED, and the FIRE
EXTINGUISHING AGENT must be REPLACED in accordance
with the maintenance schedule published in ANSUL® R-102
SYSTEM (STANDARD UL 300 LISTED).
b. The FUSIBLE LINKS in plenum and damper must be
REPLACED. This maintenance to be performed by qualified
Ansul® service personnel only.