SETTING THE DIAL

Wiring

All wiring must conform to local and national electrical codes and ordinances.

Connect in accordance with wiring diagrams provided by the equipment manufacturer. If none are provided,
the following represents a typical installation.

Adjust temperature setting by inserting a screwdriver into
open slot and turning pointer to desired temperature on
dial.

Adjustment Slot

150

°

F

66

°

C

125

°

F/52

°

C

90

°

F

32

°

C

INSTALLATION

Heating Element

L1

L2

1

2

1

2

3

4

Field

Installed

Jumper

754-1

755-1

240 VAC SIngle Element Circuit
for Full Power Disconnect
Through Both Power Conductors

Heating Element

L1

N

1

2

1

2

3

4

Field

Installed

Jumper

754-1

755-1

Upper Heating

Element

L1

L2

1

2

1

2

3

4

4

Lower

Heating Element

1

2

Field

Installed

Jumper

756-1

755-1

754-1

120 VAC Single Element
Circuit for Full Power
Disconnect

240 VAC Double Element
Limited Demand Circuit for
Full Power Disconnect
Through Both Power Con-
ductors

Two-Element

Non-Simultaneous Operation

SPECIFICATIONS

AC ELECTRICAL RATINGS:

UL and CSA recognized for resistive loads.

Temperature Ratings:

Temperature control - Variable 90

°

to 150

°

F (32

°

to

66

°

C)

Limit control - Fixed 170

°

F (77

°

C) with manual reset

Temp Control

Voltage

Limit Control

30 Amps

120-250 VAC

40 Amps

25 Amps

277 VAC

40 Amps

12.5 Amps

480 VAC

25 Amps