Connect steam boiler piping – Weil-McLain 78 User Manual

Page 15

Advertising
background image

• Installation • Start-Up • Maintenance • Parts

Connect Steam Boiler Piping

6a

General steam piping information:

Hartford Loop piping arrangement and wet
return are required for steam boilers.

• Maintain 24-inch minimum from waterline to

bottom of header (56-1/4" from bottom of
section).

• When using condensate receiver, feed pump

must be energized by boiler-mounted pump
controller.

Install piping:

Install piping as shown on page 16 for single
boilers, page 18 for multiple boilers.

Improperly piped systems or
undersized piping can contribute
to erratic boiler operation and
possible boiler or system
damage. Piping system must be
installed as shown, using pipe
sizes shown. Consult local Weil-
McLain distributor or sales office
before installing alternate piping.

1. Connect supply and return piping:

a. See table below and:

1) Size forced condensate return piping by

pump.

2) Size gravity condensate return same as

equalizer “J” pipe size.

b. Install system drain valve in lowest part of

return piping close to boiler. ASME size
requirements are shown in Table, page 13.

c. Connect cold water fill piping as shown in

Figure 14. Also shown are recommended
valves and water meter, if used. Water meter
will detect added makeup water, indicating
leaks in system.

Part No. 550-141-705

15

* Based on ASHRAE Handbook recommendations, allowing 1/2 oz. pressure drop per 100 feet of pipe for dry return.

**Based on ASHRAE Handbook recommendations, allowing 2 oz. pressure drop per 100 feet of pipe at 3.5 PSIG.

Maintain minimum 24" height from waterline to header.

Steam Boiler Pipe Size Table

Based on 2-Pipe Steam System

*Riser

* *

Pipe Size - In.

H

J

Fig.

Boiler

Header

Equalizer

No.

Model

A

B

C

In.

In.

15

378

3

3

2

15 478

4

4

2

15 578

4

4

2-1/2

16 678

3

3

4

2-1/2

16 778

4

4

4

2-1/2

16 878

4

4

4

3

16 978

4

4

6

3

17 1078-1278

4

4

4

6

3

Cold

water fill

Manual

isolation

valve

Pressure

reducing valve

(when used)

Manual

isolation

valve

Water meter

Check

valve

To condensate
return piping or
condensate
receiver
(see fig. 18,
page 17)

Figure 14 Cold Water Fill Piping

Advertising