Size the main gas line in accordance with Table 1. The figures
shown are for straight lengths of pipe at 0.5 in. W.C. pressure
drop, which is considered normal for low pressure systems. Note:
Fittings such as elbows, tees and line regulators will add to the
pipe pressure drop. Also refer to the latest version of the National
Fuel Gas Code.

TABLE 1 - GAS SUPPLY LINE SIZES (IN INCHES)*

MAXIMUM CAPACITY OF PIPE IN

CUBIC FEET PER HOUR

LENGTH

IN

FEET

1/2"

3/4"

1"

1 1/4" 1 1/2"

2"

2 1/2"

3"

4"

10

175

360 680

1400 2100 3960

6300 11000 23000

20

120

250 465

950

1460 2750

4360

7700 15800

30

97

200 375

770

1180 2200

3520

6250 12800

40

82

170 320

660

990

1900

3000

5300 10900

50

73

151 285

580

900

1680

2650

4750

9700

60

66

138 260

530

810

1520

2400

4300

8800

70

61

125 240

490

750

1400

2250

3900

8100

80

57

118 220

460

690

1300

2050

3700

7500

90

53

110 205

430

650

1220

1950

3450

7200

100

50

103 195

400

620

1150

1850

3250

6700

125

44

93

175

360

550

1020

1650

2950

6000

150

40

84

160

325

500

950

1500

2650

5500

175

37

77

145

300

460

850

1370

2450

5000

200

35

72

135

280

430

800

1280

2280

4600

LENGTH

IN

METERS 1/2"

3/4"

1"

1 1/4" 1 1/2"

2"

2 1/2"

3"

4"

3

51

105 199

410

615

1160

1845

3221

6735

6

35

73

142

278

428

805

1277

2255

4626

9

28

59

110

225

346

644

1031

1830

3748

12

24

50

94

193

290

556

878

1552

3192

15

21

44

83

170

264

492

776

1391

2840

18

19

40

76

155

237

445

703

1259

2577

21

18

37

70

143

220

410

659

1142

2372

24

17

35

64

135

202

381

600

1083

2196

27

16

32

60

126

190

357

571

1010

2108

31

15

30

57

117

182

337

542

952

1962

38

13

27

51

105

161

299

483

864

1757

46

12

25

47

95

146

278

439

776

1610

53

11

23

42

88

135

249

401

717

1464

61

10

21

40

82

126

234

375

688

1347

WARNING

THE HEATER IS NOT INTENDED FOR OPERATION AT HIGHER THAN
14.0" W.C.(3.48 kPa) - NATURAL GAS OR 14.0" W.C. (3.48 kPa) -
PROPANE GAS SUPPLY PRESSURE. EXPOSURE TO HIGHER
SUPPLY PRESSURE MAY CAUSE DAMAGE TO THE GAS VALVE
WHICH COULD RESULT IN FIRE OR EXPLOSION. IF
OVERPRESSURE HAS OCCURRED SUCH AS THROUGH IMPROPER
TESTING OF GAS LINES OR EMERGENCY MALFUNCTION OF THE
SUPPLY SYSTEM, THE GAS VALVE MUST BE CHECKED FOR SAFE
OPERATION. MAKE SURE THAT THE OUTSIDE VENTS ON THE
SUPPLY REGULATORS AND THE SAFETY VENT VALVES ARE
PROTECTED AGAINST BLOCKAGE. THESE ARE PARTS OF THE
GAS SUPPLY SYSTEM, NOT THE HEATER. VENT BLOCKAGE MAY
OCCUR DURING ICE STORMS. IT IS IMPORTANT TO GUARD
AGAINST GAS VALVE FOULING FROM CONTAMINANTS IN THE

GAS

WAYS. SUCH FOULING MAY CAUSE IMPROPER OPERATION, FIRE
OR EXPLOSION.

IF COPPER SUPPLY LINES ARE USED THEY MUST BE INTERNALLY
TINNED AND CERTIFIED FOR GAS SERVICE. BEFORE ATTACHING
THE GAS LINE, BE SURE THAT ALL GAS PIPE IS CLEAN ON THE
INSIDE.

TO TRAP ANY DIRT OR FOREIGN MATERIAL IN THE GAS SUPPLY
LINE, A DIRT LEG (SOMETIMES CALLED SEDIMENT TRAP OR DRIP
LEG) MUST BE INCORPORATED IN THE PIPING (SEE FIGURE 5).
THE DIRT LEG MUST BE READILY ACCESSIBLE AND NOT SUBJECT
TO FREEZING CONDITIONS. INSTALL IN ACCORDANCE WITH
RECOMMENDATIONS OF SERVING GAS SUPPLIERS. REFER TO
THE LATEST VERSION OF THE NATIONAL FUEL GAS CODE.

GAS PIPING AND DIRT LEG INSTALLATION

FIGURE 5.

To prevent damage, care must be taken not to apply too much
torque when attaching gas supply pipe to gas valve inlet.

Apply joint compounds (pipe dope) sparingly and only to the male
threads of pipe joints. Do not apply compounds to the first two
threads. Use compounds resistant to the action of liquefied
petroleum gases.

BEFORE PLACING THE HEATER IN OPERATION, CHECK FOR GAS
LEAKAGE.

Use soap and water solution or other material

acceptable for the purpose in locating the leaks. DO NOT USE
MATCHES, CANDLES, FLAME OR OTHER SOURCES OF IGNITION
FOR THIS PURPOSE.

DISCONNECT THE HEATER AND ITS MANUAL GAS SHUTOFF VALVE
FROM THE GAS SUPPLY PIPING SYSTEM DURING ANY SUPPLY
PRESSURE TESTING EXCEEDING 1/2 PSIG (3.45 kPa). GAS
SUPPLY LINE MUST BE CAPPED WHEN DISCONNECTED FROM
THE HEATER FOR TEST PRESSURES OF 1/2 PSIG (3.45 kPa) OR
LESS. THE APPLIANCE NEED NOT BE DISCONNECTED, BUT MUST
BE ISOLATED FROM THE SUPPLY PRESSURE TEST BY CLOSING
THE MANUAL GAS SHUTOFF VALVE.

GAS METER SIZE

Be sure the gas meter has sufficient capacity to supply the full
rated gas input of the water heater as well as the requirements of
all other gas fired equipment supplied by the meter. If gas meter is
too small, ask the gas company to install a larger meter having
adequate capacity.

NOMINAL IRON PIPE SIZES (INCHES)

INPUT IN THOUSANDS (BTU/HR)

NOMINAL IRON PIPE SIZES (INCHES)

INPUT IN KW