Electrical data, Basic unit (belt-drive) – York 2000 User Manual

Page 13

Advertising
background image

036-21564-003-A-1005

Unitary Products Group

13

ELECTRICAL DATA

-

Basic Unit (Belt-Drive)

MODEL

BCH

POWER SUP-

PLY

VOLTAGE

LIMITATIONS

(SEE NOTE 1)

COMPRESSOR

OUTDOOR

FAN

MOTOR,

FLA

SUPPLY

AIR

BLOWER

MOTOR,

FLA

MINIMUM

CIRCUIT

AMPACITY

MAX.

FUSE

SIZE,

(SEE NOTE 2)

AMPS

MAX.

HACR

BREAKER

SIZE,

AMPS

MIN.

MAX.

RLA

LRA

036

208/230-1-60
208/230-3-60
460-3-60
575-3-60

187
187
414
518

253
253
504
630

19.0

11.9

5.9
4.8

105

85
42
34

1.7
1.7
1.0
1.0

5.3
5.3
3.1
3.1

34.1
21.9

11.5
11.1

50
30
15
15

50
30
15
15

048

208/230-1-60
208/230-3-60
460-3-60
575-3-60

187
187
414
518

253
253
504
630

25.0
14.7

7.7
6.4

105
130

64
52

2.3
2.3
1.4
1.4

8.6
5.2
2.6
2.0

38.6
25.9
13.6

11.4

60
40
20
15

60
40
20
15

060

208/230-1-60
208/230-3-60
460-3-60
575-3-60

187
187
414
518

253
253
504
630

32.1
19.3
10.0

7.9

169
123

62
50

2.3
2.3
1.4
1.4

8.6
6.0
3.0
2.4

51.4
32.4
16.9
13.7

80
50
25
20

80
50
25
20

NOTES:

1. Utilization Range “A” in accordance with ARI Standard 110.
2. Dual element, time delay type.

MODEL

BCH

POWER

SUPPLY

HEATER

ACCESSORY

MODEL

NUMBER

SUPPLY

AIR

BLOWER

MOTOR

FLA

ELECTRIC HEATERS

MINIMUM

CIRCUIT

AMPACITY

MAX.

FUSE
SIZE

1

AMPS

MAX.

SIZE

HACR

2

BREAKER

AMPS

KW

STAGES

TOTAL

AMPS

036

208-1-60

2CE04510506
2CE04510706

2CE04511006
2CE04511506

2CE04512006

8.6

4.0
5.6
8.0

11.9

15.9

1
1
1
2
2

19.1
27.1
38.3
57.4
76.6

58.0
67.9
81.9

105.8
129.7

70
80
90

110

150

70
80
90

110

150

230-1-60

2CE04510506
2CE04510706

2CE04511006
2CE04511506

2CE04512006

8.6

5.3
7.5

10.6
15.9
21.2

1
1
1
2
2

22.1
31.2
44.2
66.2
88.3

61.7
73.1
89.3

116.9

144.5

70
80
90

125
150

70
80
90

125
150

208-3-60

2CE04510525*
2CE04510725*

2CE04511025
2CE04511525

2CE04512025

5.3

4.0
5.6
8.0

11.9

15.9

1
1
1
2
2

11.0

15.6
22.1
33.1
44.2

35.7
41.4
49.5
63.3
77.1

40
45
50
70
80

40
45
50
70
80

230-3-60

2CE04510525*
2CE04510725*

2CE04511025
2CE04511525

2CE04512025

5.3

5.3
7.5

10.6
15.9
21.2

1
1
1
2
2

12.7
18.0
25.5
38.2
51.0

37.8
44.4
53.7
69.7
85.6

45
50
60
70
90

45
50
60
70
90

460-3-60

2CE04510746*

2CE04511046*
2CE04511546*

2CE04512046*

3.1

6.8

10.1
13.6
19.5

1
1
1
2

8.2

12.1
16.4
23.5

21.7
26.7
31.9
40.8

25
30
35
45

25
30
35
45

575-3-60

2CE04511058
2CE04511558

2CE04512058

3.1

10.6
15.9
21.2

1
1
1

10.2
15.3
20.4

16.6
23.0
29.4

20
25
30

20
25
30

1

Dual element, time delay type

2

Standard circuit breakers may be used in Canada and on applications

over 60 amps where the heaters are separately fused.

*

These electric heaters DO NOT include a fuse box. If a fuse box is

required to meet a local code ((eg., Chicago), the following fuse
block accessories are available for field installation.

ELECTRICAL DATA

-

Heat Pump with Supplemental Electric Heat (Belt-Drive)

Electric Heat

Correction

Factors

Nominal Voltage

Voltage

KW Cap

Multipier

208

208

1.00

240

230

0.92

480

460

0.92

600

575

0.92

Fuse Block

2FB04700425

208/240 Volts

2FB04700546

460 Volts

Advertising