Ratings, Physical data basic units – York 2000 User Manual

Page 3

Advertising
background image

036-21564-003-A-1005

Unitary Products Group

3

MODELS

BCH

036

048

060

SUPPLY AIR

BLOWER

CENTRIFUGAL BLOWER (Dia. x Wd. in.)

12 x 10

12 x 10

12 x 10

FAN MOTOR HP (DIRECT-DRIVE)

1

2

3

4

1

FAN MOTOR HP (BELT-DRIVE)

1.5

1.5

1.5

INDOOR

COIL

ROWS DEEP

4

3

3

FINS PER INCH

16

15

15

FACE AREA (Sq. Ft.)

4.3

5.1

5.1

OUTDOOR

FAN

PROPELLER DIA. (in.)

22

22

24

FAN MOTOR HP

1

3

1

2

1

2

NOM. CFM TOTAL

4300

4200

4500

OUTDOOR

COIL

ROWS DEEP

1

1

1

FINS PER INCH

20

20

20

FACE AREA (Sq. Ft.)

17.1

17.1

17.1

AIR

FILTERS

(SEE NOTE)

QUANTITY PER UNIT (15" x 20" x 1")

2

2

2

QUANTITY PER UNIT (14" X 25" X 1")

1

1

1

TOTAL FACE AREA (sq. ft.)

6.6

6.6

6.6

CHARGE

REFRIGERANT 22 (lbs./oz.)

7/12

9/2

8/4

COMPRESSOR HERMETIC, RECIPROCATING (Qty)

1

1

1

NOTE: Filter racks can accommodate 1" or 2" thick filters.

RATINGS

MODEL

BCH

ARI RATINGS (SEE NOTE 1)

NOMINAL

ELECTRIC HEAT CAPACITY

(SEE NOTE 3)

KW

COOLING

PERFORMANCE

SOUND

RATING

(SEE NOTE 2)

bels

HSPF

HEATING CAPACITY

47

°F

17

°F

MBH

SEER

EER

MBH

COP

MBH

COP

240V

480V

600V

036

39

10.00

9.20

8.6

7.3

39.0

3.0

23.0

2.1

5, 7, 10, 15 & 20

7,10,15 & 20

10, 15 & 20

048

48

10.20

9.25

8.6

6.7

48.0

3.0

26.4

2.0

5, 7, 10, 15 & 20

7,10,15 & 20

10, 15 & 20

060

59

10.00

9.20

8.4

7.0

59.0

3.0

36.0

2.1 5,7,10,15,20 & 30 7,10,15,20 & 30 10,15,20 & 30

NOTE: 1. Certified in accordance with the Unitary Small Equipment certification program, which is based on ARI Standard 210/240.

2. Rated in accordance with ARI Standard 270.
3. Heaters available as accessories - all with single point power supply.

SEER = Seasonal Energy Efficiency Ratio - the total cooling output in BTU's during a normal annual usage period for cooling divided by the total electric power input

in watt-hours during the same period.

EER = Energy Efficiency Ratio-the cooling capacity in BTU's per hour (BTUH) divided by the power input in watts at any given set of rating conditions, expressed in BTUH per watt
(BTUH/watt).

COP = Coefficient of Performance - the total heating capacity provided by the refrigeration system, including circulating fan heat but excluding supplementary

resistance (BTU's per hour) divided by the total electric input (watts) x 3.412.

PHYSICAL DATA

BASIC UNITS

Unit

Size

CFM

ESP

Blower

Sound Power (dB 10

-12

Watts)

Octave Band Centerline Frequency (Hz)

SWL

dB(A)

dB(A)

@ 10 ft*

IWG

Speed

KW

63

125

250

500

1000

2000

4000

8000

038

1200

0.60

LOW

0.60

84

84

74

67

69

62

57

52

74

41

048

1600

0.55

HIGH

0.80

85

85

75

68

70

63

58

53

75

42

060

2000

0.45

HIGH

1.00

86

86

76

69

71

64

59

54

76

43

*At a distance of 10 ft from the blower

NOTE: These values have been accessed using a model of sound propagation from a point source into the hemispheric free field. The dBA values provided are to be used for reference only.

Calculation of dBA values cover matters of system design and the fan manufacturer has no way of knowing the details of each system. This constitutes an exception to any specification or guarantee

requiring a dBA value or sound data in any other form than sound power level ratings.

CAPACITY RATINGS

SOUND POWER RATINGS