Temperature Range: Cool 66-90F (19-32C), Heat 60-80F (16-27C)

Temporary Temperature Override feature: 45-minute default setting, adjustable in 5-minute increments

Humidity control: Dehumidification only, Range 50-75%, Span is 5-10%. Requires special HVAC system with
dehumidification circuit

Pre-purge capability: Span 0-7200 seconds, default is 0

CO2 control: Range 500-2000 ppm, Span 50-500 ppm

Can optionally display space humidity, CO2, and outdoor temperature

Dedicated ventilation output

Outdoor sensor option, Bard PN 8403-061, can be used to:

o Limit minimum outdoor temperature for cooling operation
o Limit minimum outdoor temperature for heat pump operation (compressor lockout)
o Inhibit electric heat operation for heat pumps above selected outdoor temperature

Remote indoor sensor option, Bard PN 8403-062, can be used to with following options:

o Use remote indoor sensor only
o Average remote indoor sensor and on-board sensor
o Highest of connected sensors
o Lowest of connected sensors

Vertical mount, mounts to standard 2x4 handy-box installed vertically or horizontally

Off-white


Controller Connections: Terminal legend
Terminal

Function

Type

Form

D

Dehumidification

Output

24VAC SPST RELAY

SC

24VAC to Relay Outputs D, A, W2

Power

A

Ventilation Call

Output

24VAC SPST RELAY

W2

2

nd

Stage Heating

Output

24VAC SPST RELAY

W1/E

1

st

Stage Heating/Emer. Heat

Output

24VAC SPST RELAY

SC

24VAC to Relay Outputs W1/E, Y2, Y1

Power

Y2

2

nd

Stage Compressor

Output

24VAC SPST RELAY

Y1

1

st

Stage Compressor

Output

24VAC SPST RELAY

Y0

Economizer

Output

24VAC SPST RELAY

SC

24VAC to Relay Outputs YO, O/B, G

Power

O/B

Reversing Valve

Output

24VAC SPST RELAY

G

Indoor Blower

Output

24VAC SPST RELAY

IN9

Not Used

ROS

Remote Occupancy Sensor

Input

Dry Contact (Input to GND)

GND

REM

Remote Temperature Sensor

Input

10K Type II Thermistor

+B

Communications

-A

Communications

OAT

Outdoor Air Temperature Sensor

Input

10K Type II Thermistor

LAS

Leaving Air Temperature Sensor

Input

10K Type II Thermistor

GND

Control Ground

L

Lockout Alarm

Input

Dry Contact (Input to GND)

Com

24VAC Common

Power

24V

24VAC Hot

Power



Bard Manufacturing Company, Inc.
Bryan, Ohio 43506
www.bardhvac.com

Form No.

F1943

May, 2012

Supersedes: F1943-212

Due to our continuous product improvement policy, all
specifications subject to change without notice.

Before purchasing this appliance, read important energy cost
and efficiency information available from your retailer.

Page

2 of 2

Advertising
This manual is related to the following products: