Selection data – York YCUL0016 User Manual

Page 10

Advertising
background image

YORK INTERNATIONAL

10

YORK INTERNATIONAL

11

FORM 150.63-EG1

Selection Data

REFRIGERANT PIPING

General

When the unit has been located in its final

position, the unit piping may be connected. Normal instal-

lation precautions should be observed in order to receive

maximum operating efficiencies. System piping should

conform to the York DX piping guide form 050.40-ES2 or

ASHRAE refrigeration handbook guidelines. All piping

design and installation is the responsibility of the user.

YORK ASSUMES NO WARRANTY RESPONSIBILITY

FOR SYSTEM OPERATION OR FAILURES DUE TO

IMPROPER PIPING OR PIPING DESIGN.

Filter driers and sight glasses are shipped loose for field

installation on each refrigerant circuit. Field refrigerant

piping can be connected to the condensing unit.

All expansion valves, liquid line solenoid valves, refrig-

erant and refrigerant piping are supplied and installed

by others.

Table 4 lists refrigerant line connections sizes per unit

model number.

REFRIGERANT LINE SIZING

Refrigerant piping systems must be designed to provide

practical line sizes without excessive pressure drops,

prevent compressor oil from being “trapped” in the refrig-

erant piping, and ensure proper flow of liquid refrigerant

to the thermal expansion valve. Considerations should

be give to:

1) Suction line pressure drop due to refrigerant flow.

2) Suction line refrigerant velocity for oil return.

3) Liquid line pressure drop due to refrigerant flow.

4) Liquid line pressure drop (or gain) due to vertical rise

of the liquid line.

Table 5 provides the pressure drops for given pipe sizes

for both liquid and suction lines. The pressure drops

given are per 100 equivalent ft. (30.5 m) of refrigerant

piping. These friction losses do not include any allow-

ances for strainer, filter drier, solenoid valve, isolation

valve or fittings

Nominal pressure drop for solenoids, sight glass, and

driers are shown in Table 2.

Table 1 includes approximate equivalent lengths for

copper fittings.

To ensure a solid column of liquid refrigerant to the expan-

sion valve, the total liquid line pressure drop should

never exceed 40 psi (276 kPa). Refrigerant vapor in

the liquid line will measurably reduce valve capacity and

poor system performance can be expected.

To allow adequate oil return to the compressor, suction

risers should be sized for a minimum of 1000 FPM (5.08

m/s) while the system is operating at minimum capacity

to ensure oil return up the suction riser. Refer to

Table 5

under column labeled Nominal Tons (KW) Unloaded.

Evaporator Below Condensing Unit

On a system where the evaporator is located below the

condensing unit, the suction line must be sized for both

pressure drop and oil return. In some cases a double

suction riser must be installed to ensure reliable oil return

at reduced loads. Table 3 indicates when a double suc-

tion riser should be used for listed pipe sizes to provide

adequate oil return at reduced loads. The calculated

information was based on maintaining a minimum of

1000 fpm (5.08 m/s) refrigerant vapor velocity.

Condenser Below Evaporator

When the condensing unit is located below the evapora-

tor, the liquid line must be designed for both friction loss

and static head loss due the vertical rise. The value of

static head loss of 5 PSI/ft.(3.4 kPa/30 cm) must be

added to the friction loss pressure drop in addition to all

pressure drops due to driers, valves, etc.

OIL TRAPS

All horizontal suction lines should be pitched at least 1/4"

per foot (2 cm/m) in the direction of the refrigerant flow

to aid in the return of oil to the compressor. All suction

lines with a vertical rise exceeding 3 feet (.91 meters)

should have a “P” trap at the bottom and top of the riser.

Suction lines with a vertical rise exceeding 25 feet (7.6

meters) should be trapped every 15 feet (4.6 meters).

REFRIGERANT CHARGE

The condensing unit is charged with a dry nitrogen hold-

ing charge. The remaining operating charge for the con-

densing unit, evaporator coil, and refrigerant piping must

be weighed in after all refrigerant piping is installed, leak

checked, and evacuated. Final adjustment of refrigerant

charge should be verified by subcooling values (refer to

section on Pre-Startup for checking subcooling).

REFRIGERANT PIPING REFERENCE

For more details, refer to ASHRAE Refrigeration Hand-

book, Chapter 2.

Advertising
This manual is related to the following products: